Permit Number: T00CM05244
Parcel: 128010010

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T00CM05244
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2000 JIM EGAN FIRE REVIEW Approved
10/24/2000 DAN CASTRO ZONING REVIEW Approved
10/25/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
10/25/2000 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1 PROVIDE PANEL LV AIC RATING 2 TRANSFORMER T1 DOESNT INDICATE GROUNDING ELECTRODE CONDUCTOR PER 250-30A(2) 1999 N.E.C. 3 PLEASE; IN THE FUTURE CALCULATE QUAD. RECEPTACLES PER 220-3B(9) (EACH DUPLEX RECEPTACLE TO BE CALCULATED AT 180 VA EACH). 4 PROVIDE TOTAL LOAD ASSESMENT IN FUTURE OF MAIN SERVICE. 5IS THIS SUITE 105 OR 106 ? (CHANGE DRAWING TO APPROPRIATE SUITE #)
10/25/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
11/01/2000 TGRIFFUS BUILDING-COMMERCIAL REVIEW Approved
11/01/2000 RAY MORGAN WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/01/2000 TAMI ACHONG APPROVAL SHELF Completed
11/01/2000 TAMI ACHONG OUT TO CUSTOMER Completed
11/01/2000 TAMI ACHONG REJECT SHELF Completed