Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T00CM05244
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/24/2000 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/24/2000 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 10/25/2000 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/25/2000 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1 PROVIDE PANEL LV AIC RATING 2 TRANSFORMER T1 DOESNT INDICATE GROUNDING ELECTRODE CONDUCTOR PER 250-30A(2) 1999 N.E.C. 3 PLEASE; IN THE FUTURE CALCULATE QUAD. RECEPTACLES PER 220-3B(9) (EACH DUPLEX RECEPTACLE TO BE CALCULATED AT 180 VA EACH). 4 PROVIDE TOTAL LOAD ASSESMENT IN FUTURE OF MAIN SERVICE. 5IS THIS SUITE 105 OR 106 ? (CHANGE DRAWING TO APPROPRIATE SUITE #) |
| 10/25/2000 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/01/2000 | TGRIFFUS | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/01/2000 | RAY MORGAN | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/01/2000 | TAMI ACHONG | APPROVAL SHELF | Completed |
| 11/01/2000 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 11/01/2000 | TAMI ACHONG | REJECT SHELF | Completed |