Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T00CM05170
Parcel: 140420120

Address:
6760 S PLUMER AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T00CM05170
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2001 DOUG WILLIAMS FLOODPLAIN REVIEW Denied See previous comment from 12/19/00 - floodplain use permit required. (D. Williams 1/25/01)
01/29/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Approved
01/30/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
02/02/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied SECOND REVIEW

E1
1) Both the HV and LV panels lack proper work clearance. See page P1 for equipment layout. Please note there is a fire extinguisher in front of panel LV. 99NEC 110-26
2/2/01: Not corrected. Although the fire extinguisher has been moved there is not 30" of work clearance parallel to the panel face extending to the floor.
2) The entire floor of the building is a class 1 div 2 area up to 18" AFF. The igniter for the water heater must be a minimum of +18" above the floor.
The transformer must be elevated or must be properly listed. See 99NEC 513-3(b) and the 2000 UL "General Information for Electrical Equipment"
book for additional information.
2/2/10: Not corrected
E3
1) It appears a size 1 starter is required for a 5 hp 208V 3 phase motor.
2/2/01: Corrected
2) The 1" conduit containing (4) #2, (1)#8 conductors is too small. Typical of 4 places.
2/2/01: Corrected
02/02/2001 TGRIFFUS WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2001 DELMA ROBEY OUT TO CUSTOMER Completed
02/07/2001 DELMA ROBEY APPROVAL SHELF Completed
02/02/2001 DELMA ROBEY REJECT SHELF Completed