Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T00CM05170
Parcel: 140420120

Address:
6760 S PLUMER AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T00CM05170
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Denied
01/03/2001 TGRIFFUS WATER REVIEW Approved
01/03/2001 RAY MORGAN WWM REVIEW Denied
12/07/2000 JIM EGAN FIRE REVIEW Approved
12/11/2000 PGEHLEN NPPO REVIEW Passed
12/19/2000 DOUG WILLIAMS FLOODPLAIN REVIEW Denied
12/27/2000 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E1
1) Both the HV and LV panels lack proper work clearance. See page P1 for equipment layout. Please note there is a fire extinguisher in front of panel LV. See 99NEC 110-26
2) The entire floor of the building is a class 1 div 2 area up to 18" AFF. The igniter for the water heater must be a minimum of +18" above the floor.
The transformer must be elevated or must be properly listed. See 99NEC 513-3(b) and the 2000 UL "General Information for Electrical Equipment" book for additional information.
E3
1) It appears a size 1 starter is required for a 5 hp 208V 3 phase motor.
2) The 1" conduit containing (4) #2, (1)#8 conductors is too small. Typical of 4 places.
12/28/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Approved
12/28/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide the F.F.E. of the wash rack. What material is the 6" sanitary sewer in the trench? 2. Water heater instalation does not comply with Secx510.1UPC1994 and Sec703.3UMC1994. 3. Provide a complete waste line isometric drawing on the plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/18/2001 DELMA ROBEY APPROVAL SHELF Completed
01/18/2001 DELMA ROBEY OUT TO CUSTOMER Completed
01/08/2001 DELMA ROBEY REJECT SHELF Completed