Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T00CM05170
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 01/03/2001 | TGRIFFUS | WATER | REVIEW | Approved | |
| 01/03/2001 | RAY MORGAN | WWM | REVIEW | Denied | |
| 12/07/2000 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/11/2000 | PGEHLEN | NPPO | REVIEW | Passed | |
| 12/19/2000 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Denied | |
| 12/27/2000 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E1 1) Both the HV and LV panels lack proper work clearance. See page P1 for equipment layout. Please note there is a fire extinguisher in front of panel LV. See 99NEC 110-26 2) The entire floor of the building is a class 1 div 2 area up to 18" AFF. The igniter for the water heater must be a minimum of +18" above the floor. The transformer must be elevated or must be properly listed. See 99NEC 513-3(b) and the 2000 UL "General Information for Electrical Equipment" book for additional information. E3 1) It appears a size 1 starter is required for a 5 hp 208V 3 phase motor. 2) The 1" conduit containing (4) #2, (1)#8 conductors is too small. Typical of 4 places. |
| 12/28/2000 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/28/2000 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide the F.F.E. of the wash rack. What material is the 6" sanitary sewer in the trench? 2. Water heater instalation does not comply with Secx510.1UPC1994 and Sec703.3UMC1994. 3. Provide a complete waste line isometric drawing on the plan. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/18/2001 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 01/18/2001 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 01/08/2001 | DELMA ROBEY | REJECT SHELF | Completed |