| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E.1 1) Remove the reference to the first panel N from the plan. 2) It appears a delta 2 should be placed adjacent to the 10kaic rating for the panel N. E.2 1) Include circuit N-26 in the multicircuit N-22,24, serving the receptacle drops E.3 1) The #6 equipment ground on the line side of the 200 amp disconnect must be increased to a #4/0 minimum. The #1 ground on the line side of the 600 amp disconnect must be increased to a minimum of parallel #1/0 copper conductors. 99NEC 250-102(c). 2) The TEP SR book indicates there is 77,400 amps available at the terminals of their transformer. Clarify how you arrived at 34,600 amps. 3) Clarify the verbiage on the left of the existing termination can. GENERAL COMMENTS 1) Please see the note on the plan limiting the approval to delta 2 only. In the future any revisions to an existing plan must be made on a fully corrected copy. These plans contain many of the original errors that were first discovered and subsequently corrected. |