Permit Number: T00CM03704
Parcel: 140420120

Address:
6824 S PLUMER AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T00CM03704
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2000 RAY MORGAN WWM REVIEW Denied
09/19/2000 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied
09/19/2000 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Site plan indicates that a backwater valve will be required. Indicate location on the plan and provide access detail. 2. Provide data sheets on Aqua Glass #613635 & IS7236SH for approved listings. 3. Minimum print size on plans is 10pt. Mechanical 1.Architectural details 2&3/A-8 do not reflect model energy code calculations. Note: EF-4 is on south side of the building-A-7 indicates it being on the North side.
09/28/2000 PHIL SEADER BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/29/2000 TAMI ACHONG APPROVAL SHELF Completed
09/29/2000 TAMI ACHONG OUT TO CUSTOMER Completed
09/29/2000 TAMI ACHONG REJECT SHELF Completed