Permit Number: T00CM00711
Parcel: 120093080

Address:
4823 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T00CM00711
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Approved
01/30/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E1.0
1) Provide fixture cuts for both the E and F type fixtures. Please note COT light ordinance prohibits any light above the horizontal plane. In addition the F type fixture does not attach to a wall, the architectural plans indicate a chain link fence surrounds the pumps.
2) Provide Model Energy lighting calculations.
E2.0
1) It appears that the 1.25" conduit from panel A to panel B should be a 1.5" minimum.
2) The 120 amp load flag attached just under panel A is incorrect. The load is approximately 174 amps.
3) The length of the service lateral is considerably shorter than 60 feet; thus the fault calculation is incorrect. You might consider using a listed/labeled fully integrated series rated system. Using UL Class RK1 fuses such systems are available for up to 100,000 amps.
02/02/2001 PHIL SEADER BUILDING-COMMERCIAL REVIEW Approved
02/05/2001 TGRIFFUS WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2001 TAMI ACHONG OUT TO CUSTOMER Completed