Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T00CM00711
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/29/2001 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/30/2001 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Denied | E1.0 1) Provide fixture cuts for both the E and F type fixtures. Please note COT light ordinance prohibits any light above the horizontal plane. In addition the F type fixture does not attach to a wall, the architectural plans indicate a chain link fence surrounds the pumps. 2) Provide Model Energy lighting calculations. E2.0 1) It appears that the 1.25" conduit from panel A to panel B should be a 1.5" minimum. 2) The 120 amp load flag attached just under panel A is incorrect. The load is approximately 174 amps. 3) The length of the service lateral is considerably shorter than 60 feet; thus the fault calculation is incorrect. You might consider using a listed/labeled fully integrated series rated system. Using UL Class RK1 fuses such systems are available for up to 100,000 amps. |
| 02/02/2001 | PHIL SEADER | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/05/2001 | TGRIFFUS | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/07/2001 | TAMI ACHONG | OUT TO CUSTOMER | Completed |