Plan Number: S17-019
Parcel: Unknown

Address:
875 W CUSHING ST

Review Status: Completed

Review Details: MINOR SUBDIVISION REVIEW

Plan Number - S17-019
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2017 MMENDIB1 START PLANS SUBMITTED Completed
05/11/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approv-Cond DATE: May 11, 2017
DUE DATE: May 15, 2017
SUBJECT: Final Block Plat
TO: T. Wayne Ashby, RLS
LOCATION: Rio Nuevo - Catepillar
REVIEWERS: Paul Baughman, PE, CFM
ACTIVITY: S17-019
SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Block Plat Package. The following items need to be addressed:
1) Per AM 2-07.5.3D please fill in the line of who is requesting the block plat.
2) Per AM 2-07.5.4F show the Floodplain areas in a surveyable and readily retraceable manner. Update General Note 6 accordingly. See also Tucson Code Section 26-8(b)(5)
3) Per UDC 8.4.5A2 and UDC 8.6.2 please provide a copy of the assurances filed under separate document with the City of Tucson for review with the next submittal of the block plat. Please see AM 2-07.5.3E for verbage to be included as part of the assurances.
If you have any comments, questions or wish to discuss new information, please call or email Loren Makus at 520-837-4927 or loren.makus@tucsonaz.gov.
05/11/2017 ALEXANDRA HINES PIMA COUNTY WASTEWATER Approv-Cond May 11, 2017

To: T. Wayne Ashby
Ashby Surveying & Drafting, Inc..

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: _______________________________________________
Debbie Ketchem, Civil Engineer Assistant - Sr.
Development Liaison Unit
Subject: Review Letter - sewer elements only
Final Plat - 1st Submittal, P17WS00044 (S17-019)
Rio Nuevo - Caterpillar
_______________________________________________________________________

Pima County Regional Wastewater Reclamation Department (PCRWRD) received this Final Plat on May 11, 2017. The following revisions are requested:

1. A Type II Capacity Letter must be issued for this project before the Final Plat can be approved.
2. Page 1: General Note #8, add "by separate instrument" after the word abandoned.
3. Page 2: Identify the new 20' sanitary sewer easement as "20' public sewer easement" or "20' public sanitary sewer easement".
4. Page 2: RWRD is requesting for the new 20' public sewer easement to be extended to the south line of the easement to the south right-of-way line of Cushing Street.
If you need further clarification of the reasoning for this request, please contact Francisco Galindo at 520-724-6733. He is currently reviewing the Sewer Improvement Plan (SIP) and the location of the sewer may need to be shifted.
The new sewer alignment would also need to be reflected on the SIP plans.

The next submittal will be the 2nd submittal for this Final Plat. The RWRD review fee for the 2nd submittal will be $50.00 (Per PC Code, Title 13.20.030.A.2).

Do not hesitate to contact me if you have any questions at (520) 724-6481.

Cc: Lorenzo Hernandez, P.E., C.E. Manager., RWRD
Francisco Galindo, P.E., RWRD
05/11/2017 ALEXANDRA HINES UTILITIES SOUTHWEST GAS Passed notified agency for information only, no response needed
05/11/2017 JVINCEN1 COT NON-DSD FIRE Approved
05/11/2017 AHINES2 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed no response needed for plat less than six lots
05/11/2017 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved Regional Traffic Engineering has no comments on the block plat and supports its acceptance.

ADOT/Regional Traffic would like the opportunity to review any traffic impact reports, for the development, because of its proximity to I-10 and the ramp system in future submittals.

Thank you.

Tom Martinez <TMartinez@azdot.gov>
05/11/2017 AHINES2 ZONING HC REVIEW Passed
05/11/2017 ALEXANDRA HINES PIMA COUNTY ASSESSOR Approv-Cond Office of the Pima County Assessor
240 N. Stone Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR

TO: City of Tucson Development Services

FROM: Suzanne Gilpin
GIS Cartographer
Pima County Assessor's Office
(520)724-4387

DATE: May 11, 2017

RE: Assessor's Review and Comments Regarding Final Plat-
RIO NUEVO-CATERPILLAR/S17-019

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Plat meets Assessor's Office requirements.
__X___ Plat does not meet Assessor's Office requirements.

COMMENTS:

" The title block in the lower right hand corner must have the number of Lots.

" There must be a Section Tie, with a bearing and dimension from the Section corner or Quarter corner to the Point of Tie on the subdivision.

" All lots must be numbered and have square footage.

NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
05/11/2017 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
05/11/2017 ALEXANDRA HINES OTHER AGENCIES PIMA ASSN OF GOVTS Passed notified agency for information only, no response needed
05/11/2017 ALEXANDRA HINES ZONING REVIEW Approved
05/11/2017 ALEXANDRA HINES OTHER AGENCIES U. S. POST OFFICE Passed notified agency for information only, no response needed
05/12/2017 AHINES2 LANDSCAPE REVIEW Approved
05/12/2017 ALEXANDRA HINES COT NON-DSD REAL ESTATE Approv-Cond The two notes for Alemeda Acequia Madre and Clearwater Drive should read: "Right of Way Vacated East of this Line" and the line should be the West Line of the Block being created. The line work for said Alemeda Acequia Madre and Clearwater Drive within Avenida Del Convento can be removed as it is all to be public right of way in the end.

The note for Cushing Street along the north side of the Block being created should simply read: "Vacated Right of Way" or "Right of way Vacated South of this Line" ....and "Existing Right of Way Line" should read "Former Right of Way Line"

The note for Cushing Street at the intersection of Cushing and Avenida Del Convento can be removed since public right of way is remaining for said streets. The line work for said Cushing Street within Avenida Del Convento can be removed as it is all to be public right of way in the end.

If Avenida Del Convento is being created by this plat, then the City (Mayor) needs to be included as a signatory on the dedication or the Rio Nuevo Multipurpose Facilities District needs to acquire title to the the proposed right of way prior to plat approval. The same goes for the public I/E easte at the SW side of Avenida Del Convento.

I do not believe the new Right of Way line for Cushing should extend east beyond the Block being created and Existing right of way line should be shown as solid.

The note for the Easterly Line of Block 13 and CA "C" should be better positioned or have arrows pointing to the line as there is an erosion set back line in the area and the note sits on top of the 30' reclaimed easement and could be confusing without the benefit of the narrative legal or record of survey.

There is at least one CoT Monitoring well that is to remain on site. Please have the well(s) identified and have the well(s) shown on the plat with an easement created for each well that is to remain and an access easement to each remaining well. The contact person for follow up on the remaining well is Thomas Ryan at 837-3713

Flood Plain limits have either changed or are in process...not sure showing old information on the plat is useful. The Contact for this issue is Fred Felix at 837-6620.

A right of entry should be issued by the City prior to allowing any construction activities on the site OR closing and recordation of the Deed conveying the property should occur.

Best Regards,

Jim Rossi, Real Estate Administrator
City of Tucson, Real Estate Division
201 N. Stone Ave. 6th Fl.
PO Box 27210
Tucson, Arizona 85726-7210
Direct: 520.837.6718
jim.rossi@tucsonaz.gov
05/12/2017 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved Tucson Electric Power has reviewed and approved the final plat for Rio Nuevo –Caterpillar.

Please call the New Construction Department at 520-918-8300 to apply for service. Submit a final set of approved plans including electrical load and offsite improvement plans to determine how TEP will serve this development. If easements are required, they will be obtained by separate instrument.

Please contact me at 520-917-8744 should you have any questions.

Thank you,

Mary Burke
Right of Way Agent III
Tucson Electric Power Co.
Mail Stop HQE613
PO Box 711, Tucson, AZ 85702
Office - 520-917-8744
Cell - 520-401-9895
mburke@tep.com
05/12/2017 ALEXANDRA HINES PIMA COUNTY ADDRESSING Approv-Cond See attachments in documents folder on PRO.

S17-019 Block Plat for Rio Nuevo - Caterpillar / 1st Submittal is being Returned for Corrections by Pima County Addressing.

The attached pdf contains Addressing’s comments.

Please let me know if you have any questions.

Thank you,

Robin Freiman
Addressing Official
Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570
05/12/2017 AHINES2 NPPO REVIEW Approved
05/12/2017 JANE DUARTE COT NON-DSD PARKS & RECREATION Approved Tucson Parks and Recreation has no comments or concerns regarding this Block Plat.

Howard B. Dutt, RLA
Landscape Architect
Tucson Parks & Recreation
(520) 837-8040
Howard.Dutt@tucsonaz.gov
05/12/2017 ALEXANDRA HINES ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

May 12, 2017
T.Wayne Ashby

Subject: S17-019 Rio Nuevo - Caterpillar Block Plat

Dear Mr. Ashby:

The above referenced project has been CONDITIONALLY APPROVED by the Community Design Review Committee. Please make any necessary corrections and submit the following documents:

1 Respond to all the review comments by Assessor, Addressing, Wastewater, Real Estate, and Engineering review staff. The executed final plat mylar can be reviewed and approved by Alexandra Hines via email for all five conditionally-approved comments.

1 Executed Final Plat Double Matte Océ or Photo Mylar.

1 Title report current within the last thirty (30) days.

1 Check made payable to "Pima County Recorder" in the amount of $20.00 per plat page plus a flat $4.00 handling fee, along with Consent to Dedicate and CC&R fees if applicable. Consent to Dedicate and CC&R fees are $9.00 for the first 5 pages and $1.00 for each additional page. If the Consent to Dedicate is also a fixture filing, there is an additional $9.00 fee. If you are unsure of the fees, please call Recorders Office at 520-740-4350.

1 Original Set of Executed and notarized CC&R's document (if applicable) and Assurance Package (if applicable).

1 Copied Set of Executed and notarized CC&R's document (if applicable) and Assurance Package (if applicable).

1 CD with Digital Copy in PDF format of executed Plat, CC&R's (if applicable) and Assurances (if applicable).

1 Provide the property owner(s) and engineering mailing address on a sheet of paper in the submittal to receive proper notification 1 week prior to the Mayor and Council Meeting.

The Planning and Development Services Department makes sure the Assurances (if applicable) are reviewed by the City Attorney's Office prior to being presented to the Mayor and Council. Plats, CC&R's and assurances must be approved at the same Mayor and Council Meeting. Please expect 5-6 weeks from the date submitted to the date scheduled for Mayor and Council approval.

Should you have any questions, please contact me at (520) 837-6975 or alexandra.hines@tucsonaz.gov.

Sincerely,

Alexandra Hines, AICP
Lead Planner

All comments for this case are available on our website at tucsonaz.gov/PRO.
Via Permits Plus/E-mail
05/12/2017 ROBERT SHERRY PLUMBING-RESIDENTIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2017 AHINES2 OUT TO CUSTOMER Completed