Plan Number: S04-141
Parcel: Unknown

Address:
2404 E RIVER RD

Review Status: Stopped

Review Details: REVISN TENT PLAT & CORE RESUB

Plan Number - S04-141
Review Name: REVISN TENT PLAT & CORE RESUB
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Stop
02/19/2008 BIANCA RAMIREZ ENGINEERING REVIEW Stopped
02/19/2008 ANY ZONING-DECISION LETTER REVIEW Stopped
02/19/2008 ANY ENV SVCS REVIEW Stopped
02/26/2008 JIM EGAN COT NON-DSD FIRE Denied The ADA and Tucson Development Standards require the clouded signs on Sheet 3 to be 7 feet to the bottom.
02/28/2008 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: RIVER WALK

S04-141



TEP has approves the revision of the Tentative Plat submitted February
19, 2008. Any additional easements required will be secured by separate
instrument.

Please forward any resubmittals of the final plat to this office.



Electric service will be provided to this subdivision in accordance with
the rules and regulations approved by the Arizona Corporation
Commission.



Please contact me at (520) 917-8745 if you have any questions.


Liza Castillo, Right of Way Agent
Tucson Electric Power Co.
Unisource Energy Services
offc-(520) 917-8745
fax-(520) 545-1416
lcastillo@tep.com
03/03/2008 FRODRIG2 PIMA COUNTY WASTEWATER Denied February 29, 2008

To: Steven Hill
Leadstar Engineering

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: River Walk, Lots 1-140, Blocks A & B and Common Areas A-F
TP/DP Rev - 1st Submittal
S04-141


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The development plan for this project cannot be approved until a copy of this letter has been received by this office.

Sheet 1: Add a General Note that states:

THIS PROJECT WILL HAVE ______ EXISTING AND______ PROPOSED WASTEWATER FIXTURE UNIT EQUIVALENTS PER TABLE 13.20.045(E)(1) IN PIMA COUNTY CODE 13.20.045(E).

And fill in the blanks with the appropriate values.

Sheet 1: Add a General Note that states:

ANY WASTEWATER DISCHARGED INTO THE PUBLIC SANITARY SEWERAGE SYSTEM SHALL MEET THE REQUIREMENTS OF THE INDUSTRIAL WASTE ORDINANCE (PIMA COUNTY ORDINANCE NO. 1991-140, AS AMENDED).

Sheet 1: Revise General Note #9 to read as follows:

THE ON-SITE SANITARY SEWERS, EXCEPT PUBLIC SEWERS WITHIN PUBLIC SEWER EASEMENTS OR RIGHTS-OF-WAY, WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS, AND IN ACCORDANCE WITH AN APPROVED OPERATION AND MAINTENANCE PLAN, IF REQUIRED. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT.

Sheet 1: Show the public and private sewer lines using different line-types, so that they can readily be distinguished from each other. Also, show and describe examples of these different linetypes in the legend on Sheet 1.

Sheet 3: All public sewer elements (manholes and sewer mains), that are located on this project or are less than 100’ from this project, should be identified with the wastewater plan and IMS numbers. The IMS numbers are the sewer element identification numbers that can be found on the PCWMD Maps and Records (5th floor) basemaps or on PCWMD and PCDOT MapGuide internet websites. Include the rim and invert elevations for the manholes.

Sheet 3: Call out the 4” HCS for each building as PRIVATE BCS and include the slope/length and material of pipe.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $100.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.





If you have any questions regarding the above-mentioned comments, please contact me.
03/10/2008 JOE LINVILLE LANDSCAPE REVIEW Denied Submit an updated landscape plan. Any change in design or land use requires a new review and approval process for the landscape plan. DS 2-07.2.0
03/13/2008 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S04-141 RIVER WALK/REVISED TENTATIVE PLAT
DATE: March 12, 2008



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:


Include legal description on all Title Blocks.
Delete all dockets, pages and owner info on Final Plat.
Label Buildings 1 & 2.


jg
03/14/2008 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
03/19/2008 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S04-141 River Walk 03/17/08

(X) Tentative Plat
() Development Plan
(X) Landscape Plan
(X) Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-04-04

NEIGHBORHOOD PLAN: General Plan

GATEWAY/SCENIC ROUTE: Yes

COMMENTS DUE BY: March 18, 2008

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies with Plan Policies
(X) See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
(X) Resubmittal Required:
(X) Tentative Plat
() Development Plan
(X) Landscape Plan
() Other



REVIEWER: msp 791-4505 DATE: March 17, 2008

Department of Urban Planning and Design Comments
S04-141 River Walk: Revisions to Tentative Plat & Core Resub
March 17, 2008

Staff offers the following comments:

The proposed revisions to the building foot prints within the O-2 zone portion of the plat may effect rezoning case C9-04-04, conditions number 8, and 14. Therefore, please provide the following;

Please provide a revised landscape plan showing the proposed building footprint changes and landscape borders for compliance review with rezoning condition number 8.

Also provide four-sided architectural building elevations of the proposed building foot prints to review for compliance with rezoning condition number 14.
03/21/2008 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: S04-141, River Walk - Commercial
2400 E. River (approximately)
Revision to S04-141 - new concept for commercial portion of subdivision

TRANSMITTAL DATE: March 21, 2008

DUE DATE: March 18, 2008

COMMENTS: NOT REVIEWED

1. Zoning was unable to provide a review, as the proposal did not match the Preliminary Development Plan (PDP) of recent rezoning case C9-07-02, and the 30 conditions listed per Mayor & Council approval of the rezoning of this site from O-2 to C-1.

Please write a letter to the attention of the Director of the Department of Urban Planning and Design, Albert Elias, inquiring as to whether this concept is a change from the C9-07-02 PDP that will require further Mayor & Council action. Include a copy of the last approved tentative plat pages 2 and 3, the proposal pages 2 and 3, and a copy of the PDP for C9-07-02. Mr. Elias will issue a response with further advisement on any process that may be required to proceed with the proposal. (Albert Elias, COT, DUPD, P.O. Box 27210, Tucson, AZ 85726)

2. Contact Patricia Gehlen, CDRC Manager, at 837-4919 for status of the current plan review and any future resubmittal requirements. Contact Judith Imhoff, 837-4895, in Rezoning for information on rezoning case C9-07-02.



C:\planning\cdrc\tentativeplat\S04-141 revision send out for change to C-1.doc