Plan Number: S04-141
Parcel: Unknown

Address:
2404 E RIVER RD

Review Status: Completed

Review Details: ASSURANCES

Plan Number - S04-141
Review Name: ASSURANCES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2005 MARILYN KALTHOFF START ASSURANCES RECEIVED Completed
10/27/2005 MATT FLICK ENGINEERING FOR ASSIGNMENT Completed TO: Patricia Gehlen; CDRC Coordinator DATE: November 23, 2005

SUBJECT: Engineering review of the River Walk Assurance Package. The activity number is S04-141.

SUMMARY: The Assurance package was received by Engineering on October 27th, 2005. Engineering has reviewed the received items and not does recommend approval of the Assurance package.


The next submittal must address the following items:

1. The complete assurances package must include a exhibit "A", the original agreement to construct (letter of credit) with exhibit "B", a list of the cost to construct each item found in exhibit "B," a copy of the warranty deed, a current title report and a location map on an 8 ½ x 11 sheet. DS Sec.2-03.7.1.G
10/27/2005 MATT FLICK ENGINEERING FOR ASSIGNMENT Completed It contains a copy of the original trust agreement and an unsigned Amendment to Trust. Both of these are typical of a third-party land trust assurances package. However, it also contains a blank Agreement to Construct based upon a Letter of Credit (& that form looks old and outdated).

Assurances accepted for review and forwarded to Jose O. for assignment.
11/23/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied TO: Patricia Gehlen; CDRC Coordinator DATE: November 23, 2005

SUBJECT: Engineering review of the River Walk Assurance Package. The activity number is S04-141.

SUMMARY: The Assurance package was received by Engineering on October 27th, 2005. Engineering has reviewed the received items and not does recommend approval of the Assurance package.


The next submittal must address the following items:

1. The complete assurances package must include a exhibit "A", the original agreement to construct (letter of credit) with exhibit "B", a list of the cost to construct each item found in exhibit "B," a copy of the warranty deed, a current title report and a location map on an 8 ½ x 11 sheet. DS Sec.2-03.7.1.G
11/23/2005 TAMI ACHONG ENGINEERING ASSURANCES RECEIVED/SENT TO CITY ATTORNEY Needs Review TO: Patricia Gehlen; CDRC Coordinator DATE: November 23, 2005

SUBJECT: Engineering review of the River Walk Assurance Package. The activity number is S04-141.

SUMMARY: The Assurance package was received by Engineering on October 27th, 2005. Engineering has reviewed the received items and not does recommend approval of the Assurance package.


The next submittal must address the following items:

1. The complete assurances package must include a exhibit "A", the original agreement to construct (letter of credit) with exhibit "B", a list of the cost to construct each item found in exhibit "B," a copy of the warranty deed, a current title report and a location map on an 8 ½ x 11 sheet. DS Sec.2-03.7.1.G