Plan Number: S03-026
Parcel: Unknown

Review Status: Completed

Review Details: FINAL PLAT REVIEW

Plan Number - S03-026
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2004 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
03/02/2004 TIM ROWE PIMA COUNTY WASTEWATER Denied March 17, 2004

TO: Derek Roberts
Arcadis

THRU: Craig Gross
City of Tucson Development Services

FROM: Dickie Fernández, E.I.T.
Pima County Development Review Division (Wastewater)

SUBJECT: Casitas del Sol Estates, Lots 1-121
Final Plat – 1st Submittal
S03-026

The above-referenced project has been reviewed on behalf of the Pima County Wastewater Management Department. The following comments are offered for your use:

SHEET 1. Include the trust name and number in the Dedication block. Once this is completed a Sewer Service Agreement will be prepared for this project.

SHEET 2. Per Pima County Standard Detail WWM A-3 and WWM 109-111, a public sewer easement will be required to the west of Lot 56 and north of Common Area A. Follow the above mentioned standard detail for proper design.

We will require a complete set of revised bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

The next submittal of this project will be the 2nd submittal. The review fee is $50 per revised sheet for the second submittal. The second submittal will include 2 revised sheets and a check for $100.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and response letter. If the number of revised sheets changes, please adjust the review fee accordingly.




If you wish to discuss the above comments, please contact me at 740-6947.





Dickie Fernández, E.I.T.
Development Review Division (Wastewater)

Copy: Project

DF/df
03/02/2004 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S03-026 CASITAS DEL SOL ESTATES/FINAL PLAT
DATE: March 2, 2004



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Correct Villarreal Avenue to Albacete Avenue on sheet 2.

Correct Bilbao Court to Oviedo Court on sheets 3 and 4.















jg
03/03/2004 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: CASITAS DEL SOL ESTATES
Lots 1-121
S03-026

Tucson Electric Power Company (TEP) has reviewed the final plat dated
February 26, 2004. TEP is unable to approve the plat at this time.

In order for this Company to approve the final plat, the following will be
required.

* The 10' Public Utility Easement strips along the front of all lots
should be dedicated to All Public Utilities.
* Remove the word FOR from the third paragraph of the dedication to
read as: .....PURPOSE OF ACCESS, INSTALLATION AND MAINTENANCE OF
PUBLIC.....

Show all requested requirements on the resubmittal of the final plat.
Submit two bluelines to the City of Tucson for TEP's final approval.


Liza Castillo
Land Management
Tucson Electric Power Company
lcastillo@tep.com
Office: (520) 917-8479
Pager: (520) 218-6565
Fax: (520) 917-8400
03/24/2004 DAVID RIVERA ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: David Rivera Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT: S03-026
Casitas Del Sol Estates, Lots 1-121, Common areas "A" and "B" and Blocks 1-9
Final Plat

TRANSMITTAL: March 24, 2004

DUE DATE: March 28, 2004

COMMENTS

1. An applicant has one (1) year from the date of approval of tentative plat to obtain approval of a final plat that complies with zoning and other development requirements in effect at the time of application. This final plat must be approved and recorded on or before March 1, 2005.

2. Please adjust the location map text height to 12 point. DS 2-03.6.1.C

3. The words Book and Page must be legible. Adjust the margins on the top and bottom and to the right to ¾ of an inch to provide adequate area for the words book and page. DS 2-03.6.1.G

4. Add a general note that states that a portion of this subdivision is subject to the conditions of rezoning per case number C9-98-01. DS 2-03.6.2.D

5. Review the Approval and Recording Data text blocks in DS 2-03.6.3.D and revise the respective text blocks on the final as noted in the development standards. DS 2-03.6.3.D

6. On sheet four label the square footage of Common Area "B". DS 2-03.6.4.C

7. The building setbacks are not required to be listed on the final plat. DS 2-03.6.4.E

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat
03/26/2004 ED ABRIGO PIMA COUNTY ASSESSOR Denied Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

RICK LYONS
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Ed Abrigo, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: March 26, 2004


RE: Assessor’s Review and Comments Regarding Final Plat
S03-026 Casitas Del Sol Estates T141334 (137-11,119-42)

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Plat meets Assessor’s Office requirements.
___X___ Plat does not meet Assessor’s Office requirements.


COMMENTS: Thank you for your submittal. Please make the following additions/corrections.
On sheet 2, most of the perimeter dimensions, bearings and curve data seems to be missing, or only partially there. There are Common Area “A”’s on the public streets that should be removed.
Please add the complete curve data; there are no radii anywhere, and central angles are needed.
On sheet 3, there is a perimeter curve with no data; the bearing on the east line of lots 41-43 is missing and there is a line in Common Area “A” that seems to close off a part of it; it needs to be removed or the area re-labeled.
On sheet 4, there are dimensions and bearings missing, as well as curve data. Look at Common Area “B” just above lot 5.
On sheet 5. Block 2 is missing dimensions and Block 3 is missing curve data.
Add the road information for Irvington Place, Irvington Road and Mission Road.
Where you have line-of-sight triangles, please cut away around the lettering; otherwise if will be illegible when the plat is reduced.
Add section lines and identify them.
If there are any questions, Please contact Susan King at 740-4391.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.






Susan C. King
03/29/2004 DOROTHY ROBLES COT NON-DSD REAL ESTATE Approved No Comments.
03/29/2004 LOREN MAKUS ENGINEERING REVIEW Denied DATE: March 29, 2004
TO: Craig Gross; CDRC Coordinator
SUBJECT: Casitas Del Sol Estates Final Plat Engineering Review
REVIEWER: Loren Makus
ACTIVITY NUMBER: S03-026


SUMMARY: The Final Plat has been reviewed by Development Services Department Engineering Division. We do not recommend approval of the Final Plat at this time. The following comments must be addressed before the Final Plat can be approved.

Final Plat Comments:
1. DS Sec.2-03.6.3.B Place the owner's signature line at the end of the Dedication.
2. DS Sec.2-03.6.5 Show all boundary data on the plat. Provide closure calculations for the subdivision.
3. Clarify Key Note 4 on Sheet 4 of 5 which does not point to a drawn feature. Also clarify the other floating arrow on the same sheet.
4. DS Sec.2-03.6.4.G Provide a no access easement for Lot 6 along Santander Avenue.
5. DS Sec.2-03.6.4.A Show and label all easements including the WAPA easement.
6. DS Sec.2-03.6.4.I: Retention/detention areas must be shown in a surveyable and readily retraceable manner. The 100-year ponding limits of the basins shall be labeled with surveyable data. The basin areas, labeled as Common Areas "A" "DRAINAGE" on the Final Plat, need clarification. In the Title Block, the common area descriptions and the basin area need to be differentiated; label the basin areas exclusively as "RETENTION / DETENTION BASIN" and label the other areas (such as channels) as "DRAINAGE".
7. Remove the off-site Q notation on Sheet 2 of 5.
8. Remove the PXXXX-XX from each sheet.
9. DS Sec.2-03.7.1.G: The final plat cannot be scheduled for Mayor and Council consideration until the financial assurances are approved. Address the following for other portions of the assurance package:
a. Revise any sheets of the assurance paperwork to reflect any change in descriptions of the common areas. The legal description of the subdivision must be the same wherever it appears in the submittal.
b. Provide AMENDMENT TO TRUST / THIRD PARTY TRUST.
c. Provide AGREEMENT TO CONSTRUCT SUBDIVISION IMPROVEMENTS / THIRD PARTY TRUST.
d. Provide copy of sample Warranty Deed.
e. DS Sec.2-03.8.1.D: Provide a copy of the updated Title Report (current within thirty days).
f. DS Sec.2-03.6.5.B: Assure that any and all easements listed in the forthcoming title report are labeled on the plat.
g. For this and future projects, please provide two 8½" by 11" location map sheets for assurance submittals that go to Mayor & Council.
h. If the descriptions of the common areas are changed on the Final Plat title block (due to above comments), the CC&R's descriptions of the subdivision common areas need to match the Final Plat title block descriptions.
i. Add items to Exhibit B explicitly stating that the linear park improvements and that the erosion protection must be included as assurable items.
If you have any questions or to set up a meeting, call me at 791-5550, extension 1161.

Loren Makus, EIT
Senior Engineering Associate
Engineering Division
Development Services