Review Status: Completed
Review Details: DEV STDS MODIFICATION REVIEW
Permit Number - DS15-25
Review Name: DEV STDS MODIFICATION REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2015 | AROMERO4 | START | PLANS SUBMITTED | Completed | |
| 10/27/2015 | BVIESTE1 | ZONING-DECISION LETTER | WRITE DECISION LETTER | Approv-Cond | This TSMR was conditionally approved on 10/28/2015 In addition to the conditions from ESD a revised development package will be needed for DP15-0036. Also the following information will need to be added to the development package: 1) TSMR case number must be added to each sheet of the development package in the lower right corner 2) Add a general note to the development package that includes the type of application, modifications requested, date of approval and conditions imposed if any. |
| 10/27/2015 | BVIESTE1 | ENV SVCS | REVIEW | Approv-Cond | The TSMR has been reviewed on behalf of the Environmental Services Dept. and is conditionally approved. Revise the plan to show the existing 5 ft. apron removed and replaced with a 10 ft. apron with rebar reinforcement of #4 bars at 12” on center both ways in 6 inch, 3,000 psi concrete. If there are any questions, I can be reached at kperry@perryengineering.net |