Permit Number: DP22-0188
Parcel: 11918030A

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP22-0188
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2022 SBEASLE1 START PLANS SUBMITTED Completed
07/28/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: TEP Cottonwood Substation
Development Package (1st Review)
DP22-0188

TRANSMITTAL DATE: July 28, 2022

DUE DATE: August 05, 2022

COMMENTS: Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is July 10, 2023.

2-06.3.0 FORMAT REQUIREMENTS

1. COMMENT: 2-06.3.5 – Remove the old PDSD Approval stamp from all sheets as an electronic stamp will be applied once the DP is approved.

2. COMMENT: 2-06.3.12 – The drawing index on sheet 1 is not complete and should include all sheets provided in the plan set.

CONTENT REQUIREMENTS

3. COMMENT: 2-06.4.2.D – The page number and the total number of pages in the package (i.e., sheet xx of xx) shall include all sheet submitted in the DP set.

4. COMMENT: 2-06.4.3 – Provide the development package case number, DP22-0188, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

5. COMMENT: 2-06.4.7.A.4 – As a general note identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

6. COMMENT: 2-06.4.7.A.6.a – Per UDC TABLE 4.8-2: PERMITTED USES - URBAN RESIDENTIAL ZONES, R-1 Zone, Utilities Land Use Group With Land Use Class/Type, Distribution System a Zoning Examiner Special Exception Procedure, Section 3.4.3 is required and shall be approved prior to approval of this DP. Provide the case number adjacent to the title block and provide a general note stating the case number, what was approved, any modifications approved and if applicable any conditions of approval.

7. COMMENT: 2-06.4.7.A.6.a – The proposed 12’ wall called out under Site Keynote 2 exceeds the allowed 10’ wall height per UDC Article 4.9.11.A.9.

8. COMMENT: 2-06.4.7.A.6.a – Provide written documentation that the requirement of UDC Article 4.9.11.A.8 has been met.

2-06.4.7.A.8 - For development package documents provide:

9. COMMENT: 2-06.4.7.A.8.a – Provide a lot coverage calculation that meets the requirements of UDC Article 6.4.3 on the plan.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

10. COMMENT: 2-06.4.9.H.5.a – Provide a vehicle parking space calculation on the plan that provides the number required and provided see UDC TABLE 7.4.4-1: MINIMUM NUMBER OF MOTOR VEHICLE SPACES REQUIRED, UTILITIES USE GROUP. Show the required parking spaces on the plan and demonstrate how dust control is provided.

If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
08/02/2022 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Passed Email from: Nicholas Jordan <Nicholas.Jordan@pima.gov>
To: CDRC
Mon 8/1/2022 3:21 PM

This project does not require review by Pima County Addressing.
Thank you

Nicholas Jordan
Site Review Project Manager - Addressing Official

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-9623
08/08/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/10/2022 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL
TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/Native Plant Preservation Section

PROJECT: Cottonwood Substation
ACTIVITY NO: DP22-0188
Address: 3210 S Cottonwood Ln
Zoning: R-1/R-2
Existing Use: disturbed vacant land
Proposed Use: Utility distribution

TRANSMITTAL DATE: August 10, 2022
DUE DATE: August 5, 2022
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.
General Note - UDC 2-10.4.1 Identification and Descriptive Data - All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.
1. The Unified Development Code (UDC) requires all new development t submit a landscape plan, UDC 7.6.2. Preparation of the landscape plan shall adhere to UDC 7.6.4. and Administrative Manual 2-10.
2. A Commercial Rainwater Harvesting plan is required UDC Technical Standards Manual - Section 4-01.0.0. and Section 5-01.0.0 Landscaping and Screening. Demonstrate how water harvesting is being maximized.
3. The landscape, water harvesting, and grading plans must match.
4. Identify curb inlets/splash pads to landscape areas on grading and water harvesting plans.
5. Please add a detail to show depressed landscape areas or indicate with notes.
6. Please provide all landscape calculations on the landscape plan, including required trees for the parking areas, Admin. Manual 2-10-4.2.A.2.c and landscape borders, UDC Technical Standards 2-10.4.2.f & g.
7. Please label the existing rights of way for all public streets, UDC 7.6.4.C.2.a.
8. Installing landscape/irrigation in the right of way requires approval from DoT&M, contact david.marhefka@tucsonaz.gov, plans cannot be approved without the department's consent.
9. A 10' interior landscape border is required adjacent to any residential zone (north). 1 tree/33'LF is required.
10. Provide an irrigation plan in accordance with UDC Admin. Manual
11. Please indicate the installation of a private submeter if a separate irrigation meter is not being provided by labeling it "irrigation only". UDC Technical Standards 4-01.6.1.A.1.
12. Address graphic conflicts on LO6, upper left corner.
13. Identify the type of irrigation controller with soil moisture gauge, tensiometer, weather station and/or evaportranspiration data. UDC Tech Standards 4-01.4.A.
14. Provide a maintenance schedule for the landscape and irrigation for this project. UDC 2-10-4.2.A.4., please be specific.
15. Please distinguish between the mitigation/salvage plants and the other required plants on the legend, symbol or any other method that would communicate the information. Please note that mitigation trees are in addition to other required trees.
16. Please provide a summary of quantities of all inventoried, mitigation and TOS plants in a manner that makes it simple to cross check between landscape and NPP plans.
17. A Landscape Architect or other qualified professional (not an engineer) is required to inventory and prepare the NPPO. UDC Section 7.7.4, Please note that Mesquite hybrids will be considered native trees, and should be included in NPP inventory UDC 7.7.6.
18. The monitor is responsible for an assessment of the condition of the site's plants one year after the final inspection has been performed on the site. The monitor shall visit the site and prepare a report on plant status, including general plant condition, the identification of plants under stress and the appropriate method to relieve the stress, and recommendations for replacement of plants that are dead or dying. Dead or dying plants must be replaced with the same size plant at a one-to-one ratio of like genus and species. Copies of the report must be submitted to the site owner/developer and to PDSD. The owner must respond to the plant needs as outlined in the status report within six months of report submittal or within a shorter period if required to improve the health of stressed plants and prevent plant loss.
19. Please identify the project monitor prior to any grading activities, UDC 7.7.5. On-monitoring of all aspects of site clearing, grading, plant protection, preservation, salvage, and mitigation must be provided during project construction at the expense of the developer for all residential development that is over five acres and for all commercial and industrial development that is over one acre . The monitoring must be performed by an individual who is qualified in arid lands native plant resource identification and protection as specified in UDC Section 7.7.4.D, Professional Expertise. The monitor must provide periodic progress reports to the developer outlining the status of work accomplished and any problems encountered. A copy of these reports must be submitted to the PDSD for the project file.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff

If you have any questions, please contact me at anne.warner@tucsonaz.gov
09/06/2022 JPEELDA1 FIRE REVIEW Reqs Change Fire hydrants shall be located within 400 ft of new structures. IFC 2018, Chapter 5, Section 507.5.1 and also in accordance with IFC Appendix D. Please show new and existing fire hydrant locations on the plans.



Fire department apparatus access lanes shall be 20’ wide. IFC 2018, Chapter 5, Section 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of 20’, exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of 15’ (TFD modification from 13 to 15’)



TFD requires that gates across an apparatus access road be 20’ wide and if powered have a KNOX Gate key switch and KNOX Box located at the gate. This note shall be added to your drawings.

Questions:
Jennifer Peel-Davis
Fire Plans Examiner
Tucson Fire Department
520-837-7033
Jennifer.Peel-Davis@Tucsonaz.gov
09/07/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. Per Admin Manual 2-06.4.1 - Include on the cover page the name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.
2. The drainage report mentions recommendations from PCRFCD for the rock riprap bank protection. Does this include the 6' toe down depth shown on the detail or was that calculated separately, and if so show the calculation.
3. Additional comments provided by Eric Shepp from Pima County:
1) Widen channel to west downstream of Cottonwood Lane to create a terrace for the planting of the landscaping that can take advantage of the offsite flows.
2) Add more plant to the water harvesting basin to provide a better scree from the Loop and take advantage of the water.
3) A Facility Impact Permit from the District shall be obtained prior to any Loop or other work on District property.


Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
09/08/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change email from: COTDSDPermits
To: Kevin Letendre
09/08/2022

Returned for Corrections: DP22-0188
Site/Grading/Swppp/Floodplain - Cottonwood Substation, Tucson Electric Power Company.
3210 S COTTONWOOD LN

FEE BALANCE: $ 5,446.49
ONLINE PAYMENTS
** If the online amount doesn't match "Fee Balance" above, check again in a few hours **
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this blank
4- "Continue"
5- In the Pay column - check the boxes

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on the blue tab
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter

3. UPLOAD documents to Filedrop:
- Comment Response Letter (your response to REQUIRES CHANGE comments)
- Plan Set (all pages, full set, even if no changes were made)
- Documents requested by review staff

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)


Sharon Beasley
Certified Permit Specialist

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov
(for development packages, land splits, Thursday Presubmittal meetings)
Email: PDSDinquiries@TucsonAz.gov
(for building permits)