Permit Number: DP22-0172
Parcel: 114512060

Review Status: Completed

Review Details: GRADING

Permit Number - DP22-0172
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2022 STEVE SHIELDS ZONING REVIEW Reqs Change UNITL THE REVISION TO DP21-0174 IS APPROVED ZONING CANNOT APPROVE THIS GRADING PLAN.
08/01/2022 AWARNER1 NPPO REVIEW Approved
08/03/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change Development Package Comments:
Sheet 1
1. Provide a 3" by 5" block in the lower right corner of the plan adjacent to the title block for use by Pima County Addressing.
2. Provide the name and date of the geotechnical report. Provide the name, address, and phone number of the firm who prepared the report.
3. Provide the site boundary perimeter information.
4. Provide the right-of-way of adjacent to the site. Include width dimensions of paving, curbs, and sidewalks.
5. Remove "PRELIMINARY" from seal, typical all sheets.
6. Please include drainage report with next submittal.

Sheet 2
7. Add leaders to the grading/paving notes for clarification.
8. Provide slope at all proposed curb access ramps.
9. Provide handrails at access ramps that exceed 5%.
10. Provide cross slope on the proposed sidewalk to verify 2% max.
11. Callout all high points.
12. Provide a cross section of the drive aisles/parking.
13. Add truncated domes at the ramp landing east of building #1.
14. Please include proposed storm drain pipe slope.

Sheet 3
15. Provide a cross section of the driveway east of building #3.
16. Please provide the cross slope of proposed sidewalk to verify the it doesn't exceed 2%.
17. Please avoid overlapping text.
18. Please verify that 12" "V" opening can convey 2' bottom width channel and associated drainage area.
19. Provide WSEL for all basins.

Sheet 4
20. Callout curb ramp standard details as applicable.
21. Add handrails at all ramps with a slope greater than 5%.
22. Add invert elevation of storm drain at splash pad.
23. Evaluate the need for sidewalk scupper at low point southeast of building #17.

Sheet 5
24. Provide slope at all ramps.
25. Include slope on all access ramps and reference applicable standard detail.
26. Provide invert elevation of storm drain at splash pad.
27. Call out spot elevations at all sidewalk scuppers.
28. Include a landing of no more than 2% in all directions between both ramps located southwest of building #6.
29. Please provide temporary drainage (private) until Phase 2 is completed.

Sheet 6
30. Call out applicable curb ramp standard details.
31. Include a landing with a slope less than 2% in all direction between ramps (review area NW of Bldg #14).

Sheet 7
32. Please include slope and length of all storm drain pipes.
33. Please provide horizontal control for channel.


Review and Comments provided by third party engineer reviewers under contract with the City of Tucson. For Questions or Concerns contact:
Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
08/19/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
To: Marty Magelli

REVIEW NOTICE

Returned for Corrections: DP22-0172
Grading/Swppp - The Place at Mason Ranch Apartments.
2945 N BEAR CANYON RD

FEE BALANCE: $ 3,191.90
Please pay at a minimum, the REVIEW category fees.
A payment is required before your next submittal.

ONLINE PAYMENTS
** If the online amount doesn't match "Fee Balance" shown above, check back in a few hours **
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this field blank
4- "Continue"
5- In the Pay column - check the boxes
6- "Continue"

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter

3. UPLOAD A RESUBMITTAL to Filedrop:
- Comment Response Letter (your response to REQUIRES CHANGE comments)
- Plan Set (all pages, full set, even if no changes were made)
- Any other documents requested by review staff

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)
- Select "PLANS" for all documents


Sharon Beasley, Certified Permit Technician

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov
(for development packages, land splits, Thursday Presubmittal meetings)
Email: PDSDinquiries@TucsonAz.gov
(for building permits)