Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP22-0156
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/22/2022 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 06/27/2022 | SBEASLE1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Passed | Email from: Nicholas Jordan <Nicholas.Jordan@pima.gov> on behalf of Addressing <Addressing@pima.gov> To: CDRC Thu 6/23/2022 5:00 PM Pima County Addressing does not need to be part of this review. Thank you Nicholas Jordan Site Review Project Manager - Addressing Official |
| 06/30/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/08/2022 | AWARNER1 | LANDSCAPE | REVIEW | Approved | |
| 07/08/2022 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Samuel Rogers - Planner PDSD Zoning Review Section PROJECT: Clyton Warehouse Development Package (1st Review) DP22-0156 TRANSMITTAL DATE: 07/08/2022 DUE DATE: 07/08/2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is June 10, 2023. SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) Section CONTENT REQUIREMENTS 1. COMMENT: 2-06.4.3 - Provide the development package case number, DP22-0156, and any applicable relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) adjacent to the title block on each sheet. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. Zoning and Land Use Notes 2. COMMENT: 2-06.4.7.A.7 - If the property is part of a subdivision plat that is being reviewed or has been recorded, provide the case number in the lower right corner of each sheet. As a general note, indicate whether the project is part of a Flexible Lot Development (FLD), condominium, or another similar type project. 2-06.4.8 - Existing Site Conditions The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided. 3. COMMENT: 2-06.4.8.B - Show any easements on the property, if applicable, with the recordation information, location, width, and purpose of all easements. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes 4. COMMENT: 2-06.4.9.H.5.c - Per Table 7.5.5-A, Commercial Storage uses of less than 50,000 SF and without direct vehicular access are required to have 1 Type A loading space. If you have any questions about this transmittal, Contact Samuel Rogers at (520) 837-6932 or by email Samuel.Rogers@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 08/08/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Plans shall show the fire sprinkler line We will need the type of construction to figure out fire flow required for the building and the occupancy type. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner |
| 08/23/2022 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | 1. Show the onsite maneuverability of the waste collection vehicle with dimensions. The max distance for the vehicle to back up is limited to 80' per code. 2. Check your units on the First Flush volume requirement calcuations in the drainage report - square ft times cubic feet per acre doesn't equate to cubic feet. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 08/23/2022 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email from: COTDSDPermits to: lisa bowers REVIEW NOTICE Returned for Corrections: DP22-0156 Site/Grading - Clayton Warehouse. Fee Balance: $0 (zero) YOUR NEXT STEPS 1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW 2. Title your next submittal documents accordingly, example: 2_Comment Response Letter 3. UPLOAD documents to Filedrop: - Comment Response Letter (your response to REQUIRES CHANGE comments) - Plan Set (all pages, full set, even if no changes were made) - Any other documents requested by review staff FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp - "Existing Application" - "Permit Number" field: enter the number (and any notes for our staff) Sharon Beasley, Certified Permit Technician City of Tucson, Planning & Development Services Dept. Email: COTDSDpermits@TucsonAz.gov (for development packages, land splits, Thursday Presubmittal meetings) Email: PDSDinquiries@TucsonAz.gov (for building permits) |