Permit Number: DP21-0313
Parcel: 13819039A

Address:
402 W MEDINA RD

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Permit Number - DP21-0313
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2022 JPEELDA1 COT NON-DSD FIRE Reqs Change The building id 6,080 and will require a fire flow of 2,000 GPM for 2 hours. Please provide a letter from TW stating that the 2,000 GPM can be met. If the 2,000 GPM cannot you will need to instll fire sprinklers in the building and that shall be shown on the DP. Also, the 2,000 GPM will require the use of 2 hydrants. The drawings only show 1 hydrant.
Provide diagram of hose distance from hydrant to the furthest portion of the building as the hose lays and the distance.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
01/14/2022 SBEASLE1 COT NON-DSD TRAFFIC Approved Email from: David Stiffey
To: CDRC
Fri 1/14/2022 1:46 PM

No Comments

David Stiffey
City of Tucson
Dept. of Transportation & Mobility
02/28/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change 1. The project location map on the cover sheet needs to cover approximately 1 sq mile and be drawn at a minimum scale of 3" = 1 mile per Admin Manual 2-06.4.4.
2. Provide a back-up spur for the last parking space on the east side of the parking lot per UDC article 7.4.6.F.4.
3. When was the existing CMU wall installed? Both the aerial and street view along with the lot split and presub submittals all show an existing chain link fence. Was there a site review for the CMU wall?
4. Show all points of drainage off the roof of the proposed building and where the runoff is being directed to.
5. Show on the grading plan the depressed water harvesting areas delineated with more spot grades and or contours so that it is clear they are depressed 6-9 inches as indicated on the water harvesting plan.
6. The drainage report notes that blocks from the CMU wall will be removed to allow water to pass through the northwest corner of the site. On the grading plan a flow arrow is shown passing through the wall on the southeast corner. Please clarify if and how water will flow through the wall at that area.
7. On the drainage report include an exhibit to go along with the first flush calculations that help illustrate the numbers used in the spreadsheet calculations. The exhibit should include such elements as: undisturbed areas delineated and sq footage, disturbed areas delineated and sq footage, impervious surfaces delineated and sq footage, non-contributing basins with landscape delineated and sq footage, stormwater harvesting basins including first flush delineated and sq footage, stormwater harvesting basin #s, flow direction, and water shed #s.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
03/01/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Dan White
Tue 3/1/2022 12:38 PM

REVIEW NOTICE
Returned for Corrections: DP21-0313

DESCRIPTION: Tentative Plat - Sunshine DTA Adult Day Care Facility. 402 W MEDINA RD

Fee Balance: $0 (zero) Thank you for the payment.

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab to see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. UPLOAD A RESUBMITTAL and include:
1) Comment Response Letter (your response to REQUIRES CHANGE comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your SECOND submittal documents according to this example: 2_Comment Response Letter

FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- Select "Existing Application"
- In the "Permit Number" field, enter the number and, if applicable, any notes for our staff
- Select "PLANS" for all documents for quicker downloading of your documents on our end

Thank you.
Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov
12/06/2021 SBEASLE1 UTILITIES SOUTHWEST GAS Passed
12/06/2021 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed
12/06/2021 SBEASLE1 START PLANS SUBMITTED Completed
12/06/2021 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
12/17/2021 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved (The TEP Facilities Map, TEP Development package redline, and TEP Approval Letter can be viewed in the Documents section of PRO)

Email from: Design Admins <DesignAdmins@tep.com>
TO: CDRC
Thu 12/16/2021 3:44 PM
Attached is our response letter for Sunshine DTA, DP21-0313

Thank you,
Conor Mahoney, Design Administrator, OH201
Desk: (520) 918-8388
Cell: (520) 404-8437
12/17/2021 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change (The ATTACHED PDF mentioned below can be viewed in the "Documents" section of PRO: "Pima Co Addressing, review comments, first submittal")

Email from: <Addressing@pima.gov>
TO: CDRC
Fri 12/17/2021 11:17 AM

Sunshine DTA, 1st Submittal Review: DP21-0313 is being Returned for Corrections by Pima County Addressing.
The attached pdf contains Addressing’s comments.
Please let me know if you have any questions.

Thank you,
Robin Freiman, Addressing Official

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570
12/20/2021 SAMUEL ROGERS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Samuel Rogers - Planner
PDSD Zoning Review Section

PROJECT: Sunshine DTA, Tentative Plat
Development Package (1st Review)
DP21-0313

TRANSMITTAL DATE: 12/20/2021
DUE DATE: 21/20/2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is November 22, 2023.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

2-06.3.0 FORMAT REQUIREMENTS

1. 1. COMMENT: 2-06.3.6 - Provide an additional blank three-inch by five-inch block in the lower right corner of the plan adjacent to the title block on the first sheet of the development package. Both Pima County Addressing and the City will need to stamp.

CONTENT REQUIREMENTS

2. COMMENT: 2-06.4.1 - The name, mailing and email addresses, and phone number is required to be provided for the Owner.


3. COMMENT: 2-06.4.2.B - Provide a brief legal description and a statement as to whether the project is a re-subdivision are to be provided in the title block.


4. COMMENT: 2-06.4.2.C - Provide the number of proposed lots as a general note.

5. COMMENT: 2-06.4.3 - Provide the development package case number, DP21-0313, adjacent to the title block on each sheet.

6. COMMENT: 2-06.4.4.C - Provide the section corners on the project location map.


2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

Zoning and Land Use Notes

7. COMMENT: 2-06.4.7.A.2 - Provide the gross area of the entire site and the proposed area if the proposed lots.

8. COMMENT: 2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC for each of the proposed parcels.

9. COMMENT: 2-06.4.7.A.5 - List the total number of units/lots proposed

10. COMMENT: 2-06.4.7.A.6.a - List additional applications and overlays, by case number (if applicable), in lower right corner of each sheet.

11. COMMENT: 2-06.4.7.A.7 - If the property is part of a subdivision plat that is being reviewed or has been recorded, provide the case number in the lower right corner of each sheet

2-06.4.7.A.8 - For development package documents provide:

12. COMMENT: 2-06.4.7.A.8.a - Provide the floor area for each building on each of the proposed parcels.

13. COMMENT: 2-06.4.7.A.8.b - Provide the percentage and area in square feet of all building and accessory building coverage for each lot individually.

14. COMMENT: 2-06.4.7.A.8.c - Provide the percentage of building, lot area, or vehicular use area expansion.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

15. COMMENT: 2-06.4.8.A - For each proposed lot, provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.

16. COMMENT: 2-06.4.8.B - if applicable, all easements shall be drawn on the plan.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

17. COMMENT: 2-06.4.9.A - Draw in all proposed lot lines with approximate distances and measurements.

18. COMMENT: 2-06.4.9.B - Identify each block or lot by number within the subdivision boundary and include the approximate square footage of each

19. COMMENT: 2-06.4.9.E - Proposed land splits or existing lot lines shall be drawn on the plan with dimensions and the identification number and approximate square footage of each lot.

20. COMMENT: 2-06.4.9.H.5.a - A back-up spur must be provided at the end of each row of parking if no ingress or egress is provided at that end. Provide a back-up spur at the east end of the proposed Adult-Day Care.

21. COMMENT: 2-06.4.9.H.5.d - A minimum of 2 long-term bicycle parking spaces are required.

22. COMMENT: 2-06.4.9.O - For each proposed lot, show all applicable building setback lines.

23. COMMENT: 2-06.4.9.Q - For each proposed lot, provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

24. COMMENT: 2-06.4.9.W - Indicate the locations and types of proposed signs. Any signs will be permitted under a separate permit.


If you have any questions about this transmittal, Contact Samuel Rogers at (520) 837-6932 or by email Samuel.Rogers@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
12/22/2021 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved Email from: Howard Dutt
To: CDRC
Tue 12/21/2021 11:53 AM

No existing or proposed Tucson Parks and Recreation facilities are affected by this development.

Howard B. Dutt, RLA
Landscape Architect
Tucson Parks and Recreation
(520) 631-2030
12/28/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the site drawing to show the proposed point of connection for the building sewer. Reference Section 107.2.1, IBC 2018.
2. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.
12/29/2021 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL
TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/Native Plant Preservation Section

PROJECT: Sunshine DTA
ACTIVITY NO: DP21-0313
Address: 402 W Medina St
Zoning: R-1
Existing Use: vacant, graded
Proposed Use: Adult Day Care, Commercial Services Group

TRANSMITTAL DATE: December 29, 2021
DUE DATE: December 20, 2021
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.
1. Please label the existing right of way for Medina Rd UDC 7.6.4.C.2.a.

2. Additional plants are required to meet the required 50% vegetative cover at two years growth, UDC 7.6.4.C.2.e.

3. Please add/call out soil moisture gauge/tensiometers and rain shut-off device on irrigation plans and details. UDC Tech Standards 4.01-2.A.

4. Provide a detail to show tree planting with root barrier adjacent to walkways.

5. Provide a maintenance schedule for the landscape and irrigation for this project. UDC 2-10-4.2.A.4., please be specific.

6. A Commercial Rainwater Harvesting plan is required to meet 50% of the landscape water needs. UDC Technical Standards Manual – Section 4-01.0.0. and Section 5-01.0.0 Landscaping and Screening.

7. Adherence to the Low Impact Development Standards outlined in Section 5 of the PCRFCD Design Standards for Stormwater Detention and Retention is required and shall work in conjunction with the Commercial Rainwater Harvesting design. https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Flood%20Control/Rules%20and%20Procedures/Stormwater%20Detention-Retention/dssdr-manual-board-version-201511.pdf

8. Grading, hydrology, and landscape plans must be integrated to make maximum use of site storm water runoff for supplemental on-site irrigation purposes. The landscape plan shall indicate use of all runoff, from individual catch basins around single trees to basins accepting flow from an entire vehicular use area or roof area. UDC 7.6.6.C.2. The landscape, water harvesting, and grading plans must match.

9. Identify the point of drainage off roof areas, amount of flow, and disposition of flow.

10. Identify curb inlets/splash pads to landscape areas on water harvesting or landscape plans.

11. Indicate basin inlets/outlets on both landscape and water harvesting plans. Provide spot elevations.

12. Retention/detention basins should be designed naturally and organically, whenever practicable.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff

If you have any questions, please contact me at anne.warner@tucsonaz.gov