Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2021 SBEASLE1 START PLANS SUBMITTED Completed
10/21/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: The Specialists – New Building
Development Package (1st Review)
DP21-0261

TRANSMITTAL DATE: October 21, 2021

DUE DATE: October 28, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is September 28, 2022.

2-06.2.0 APPLICATION SUBMITTAL REQUIREMENTS

1. COMMENT: 2-06.2.4 – Remove all references to building codes from the DP as building code will not be reviewed during this process.

CONTENT REQUIREMENTS

2. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0261, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

3. COMMENT: 2-06.4.7.A.4 – Under “DEVELOPMENT DATA” the use is listed as “VEHICLE SERVICE” vehicle service is not a use listed in the UDC. Provide a use as listed in the UDC, it appears that you are proposing Automotive Service and Repair – Major. Per UDC Table 4.8-7: PERMITTED USES - SPECIAL USE ZONES (2): NC, RVC, AND MU ZONES, Commercial Services Land Use Group With Land Use Class/Type: Major Service and Repair (excluding bodywork and paint-booths) requires a Zoning Examiner Special Exception Procedure, Section 3.4.3. The special exception will need to be submitted and approved prior to approval of the DP.

4. COMMENT: 2-06.4.7.A.6.a – Once the required special exception is approved provide the case number adjacent to the title block on all sheets and provide a general note stating the case number, date of approval, and if applicable conditions of approval.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

5. COMMENT: 2-06.4.8.C - The following information regarding Wegner shall be provided: the right-of-way width, dimensioned width of paving, curbs, curb cuts, and sidewalks.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

6. COMMENT: 2-06.4.9.H.5 – Provide a fully dimensions vehicle use area, additional comments maybe forth coming.

7. COMMENT: 2-06.4.9.H.5 – Provide a fully dimensioned back-up-spur at the east end of the vehicle use area that meets the requirements of UDC Article 7.4.6.F.4.

8. COMMENT: 2-06.4.9.H.5.a – Per UDC Article 7.4.6.D.2.b Minimum Width Requirement When Adjacent to Barrier. A motor vehicle off-street parking space must have a minimum width of ten feet when the side(s) of the parking space abuts a vertical barrier over six inches in height, other than a vertical support for a carport. That said demonstrate that the eastern most vehicle parking space, on the north side of the PAAL meets this requirement.

9. COMMENT: 2-06.4.9.H.5.a – The vehicle overhang dimension shown on detail 8, sheet 5 does not meet the requirements of UDC Article 7.4.6.H.3.

10. COMMENT: 2-06.4.9.H.5.c – Provide a mounting height for from the bottom of the van accessible sign on the detail. This dimension should be 7’-0”.

11. COMMENT: 2-06.4.9.H.5.d – The short- & long-term bicycle parking space calculation shall show the number required & provided.

12. COMMENT: 2-06.4.9.H.5.d – The required number of short-term bicycle parking spaces is not correct. Per UDC Table 7.4.8-1: Minimum Required Bicycle Parking Spaces, COMMERCIAL USE GROUP, standard minimum parking formula,2 short term are required, see UDC Article 7.4.3.A.2.

13. COMMENT: 2-06.4.9.H.5.d – Keynote 11 calls out “BICYCLE PARKING IN CONFORMANCE WITH COT UDC SECTION 7.4.9, SEE DETAIL” but no keynote is provided on the plan and no detail was provided. Show the location of the proposed short- & long-term bicycle parkin on the plan and provide a short- & long-term bicycle parking detail that clearly demonstrates that all requirements of UDC Articles 7.4.9.B.1 & B.2, 7.4.9.C & 7.4.9.D are met.

14. COMMENT: 2-06.4.9.Q – Provide the height and correct use of the building within the footprint of the building.

15. COMMENT: 2-06.4.9.R - As you are allowing parking vehicles to overhang the sidewalk along the south side of the site demonstrate that a 4’-0” side is maintained when a vehicle overhangs the sidewalk. At a minimum the sidewalk either needs to be 6’-6” wide or wheel stops provide that meet the requirements of UDC Article 7.4.6.H.3 need to be installed.

16. COMMENT: 2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Also provide a general note stating “ALL SIGNAGE REQUIRES SEPARATE PERMITS.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
10/26/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site drawing to include the following existing utility information:
a. The location of water lines, and fire hydrants.
b. The location and size of sanitary sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
c. The proposed point of connection to the existing public sewer.
d. The locations of gas lines, electric and telephone lines, poles, and communications cables, on-ground junction boxes, and streetlights.
e. Any existing or proposed utility easements
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018
11/02/2021 AWARNER1 LANDSCAPE REVIEW Reqs Change CDRC TRANSMITTAL
TO: Planning and Development Services Department, Plans Coordination
FROM: Anne Warner, RLA
PDSD Landscape/Native Plant Preservation Section

PROJECT: The Specialist
ACTIVITY NO: DP21-0261
Address: 4342 N Wegner Ln
Zoning: MU
Existing Use: disturbed, vacant land
Proposed Use: Automotive service

TRANSMITTAL DATE: November 2, 2021
DUE DATE: October 28, 2021
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed.
This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.
1. UDC 2-10.4.1 Identification and Descriptive Data
A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

2. An approved Native Plant Preservation Plan Sections 7.7.4 is required or a request for an exception from the Native Plant Preservation requirements in accordance with Sections 7.7.3.D.3 & .4 of the Unified Development Code (UDC) and Admin. Manual Section 2-11.0.0 is required prior to Grading Plan approval.

3. Please provide all landscape calculations for required trees for the parking areas, Admin. Manual 2-10-4.2.A.2.c, UDC Technical Standards 2-10.4.2.f & g.

4. Preparation of the landscape plan shall adhere to the requirements found in UDC Admin Manual 2-10.3.0 and 4.0.

5. Using the 40’ trunk to parking space requirement or placing trees only along the edge of a parking area does not meet the intent of the UDC. The intent is to provide as much shade on the asphalt as possible, and the requirement is 1 tree per 4 parking spaces; trees are expected to be placed within the parking area itself. Trees are to be distributed evenly throughout the parking area, UDC 7.6.4.1.B.1, UDC Technical Standards Manual 5-01-.3.2 and UDC 7.6.4.B.1.a.

6. Please label the existing and future rights of way for Wegner Ln UDC 7.6.4.C.2.a.


7. Per Admin. Manual 2-10-4.2.D, provide page/detail reference to civil drawings/details that show bike racks, walkways, and screening/retaining walls on landscape plans. See civil drawing is not sufficient.

8. Provide a maintenance schedule for the landscape and irrigation for this project. UDC 2-10-4.2.A.4., please be specific.

9. An irrigation plan and specifications are required per UDC Administration Manual 2-10.4.2.C and Technical Standards Manual Section 4-01.4.2, Irrigation Standards.

10. Identify water meter and POC on irrigation plan.

11. Please add/call out soil moisture gauge/tensiometers and rain shut-off device on irrigation plans and details. UDC 4.2.A.
12.

13. A Commercial Rainwater Harvesting plan is required UDC Technical Standards Manual – Section 4-01.0.0. and Section 5-01.0.0 Landscaping and Screening.

14. Adherence to the Low Impact Development Standards outlined in Section 5 of the PCRFCD Design Standards for Stormwater Detention and Retention is required and shall work in conjunction with the Commercial Rainwater Harvesting design.
https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Flood%20Control/Rules%20and%20Procedures/Stormwater%20Detention-Retention/dssdr-manual-board-version-201511.pdf

15. Grading, hydrology, and landscape plans must be integrated to make maximum use of site storm water runoff for supplemental on-site irrigation purposes. The landscape plan shall indicate use of all runoff, from individual catch basins around single trees to basins accepting flow from an entire vehicular use area or roof area. UDC 7.7.6.C.2. The landscape and grading plans must match.

16. Identify the point of drainage off roof areas, amount of flow, and disposition of flow.

17. Identify curb inlets to landscape areas.

18. Retention/detention basins should be designed naturally and organically, whenever practicable.

19. Modify details to show depressed landscape areas.

20. Provide a detail to show tree planting with root barrier adjacent to walkways.



RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items requested by review staff

If you have any questions, please contact me at anne.warner@tucsonaz.gov
11/08/2021 JPEELDA1 FIRE REVIEW Reqs Change Drawings shall show existing fire hydrant and the distance to the furthest part of the building as the hose lays not the crow flies. Distance shall not exceed 400'. If the distance exceeds 400' you shall either install a fire hydrant and or install fire sprinklers.

Jennifer Peel-Davis
520-837-7033
Jennifer.Peel-Davis@Tucsonaz.gov
12/23/2021 LOREN MAKUS ENGINEERING REVIEW Needs Review 1. There are several locations in the plans where data is not completed or is different from other locations in the plans. Please make sure the plans are consistent.
2. Show roof drainage directions. Make sure roof drainage is not directed over sidewalks.
3. Show how drainage patterns and grading will provide for maximizing water harvesting.
Loren Makus
loren.makus@tucsonaz.gov
12/27/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: R. Roberts
Cc: Civil Design Group
Mon 12/27/2021 8:24 AM

Returned for Corrections: DP21-0261

DESCRIPTION: Site/Grading - The Specialists. New building. 4342 N WEGNER LN

FEE BALANCE: $ 895.88
ONLINE PAYMENT
If amount doesn't match "Fees Due", check back in a few hours
https://www.tucsonaz.gov/pdsd/fees
1- Click on: Pay Planning & Permit Fees
2- Enter Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave this field blank
4- "Continue"
5- In the Pay column - check the boxes
6- "Continue"

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab to see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. UPLOAD A RESUBMITTAL and include:
1) Comment Response Letter (your response to REQUIRES CHANGE comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your SECOND submittal documents according to this example: 2_Comment Response Letter

FILEDROP for your Resubmittal
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- Select "Existing Application"
- In the "Permit Number" field, enter the number and, if applicable, any notes for our staff


Thank you.