Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP21-0115
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2021 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 05/10/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/03/2021 | JPEELDA1 | FIRE | REVIEW | Approved | Unclear as to scope of work as shown. Shows that they are demolishing a structure but associated building plan shows that they are adding a new building. Please deifne actual scope of work and intenet on your drawings. Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |
| 06/03/2021 | JPEELDA1 | FIRE | REVIEW | Approved | The plans for T21CM01003 show what they are doing much better. |
| 06/07/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: Maddock Machinery – Building Addition Development Package (1st Review) DP21-0115 TRANSMITTAL DATE: June 7, 2021 DUE DATE: June 7, 2021 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is May 06, 2021. CONTENT REQUIREMENTS 1. COMMENT: 2-06.4.3 – Provide the development package case number, DP21-0115, adjacent to the title block on all sheets. 2. COMMENT: 2-06.4.4.C – Provide the following on the location map, section, township, and range; section corners. 3. COMMENT: 2-06.4.5 - 4. COMMENT: 2-06.4.6 – 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 5. COMMENT: 2-06.4.7.A.4 - The Use Specific Standards listed under General Note 3 is not correct, remove “.4” from the note. 6. COMMENT: 2-06.4.7.A.6.a – Provide a general note stating “THIS PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE(S) CRITERIA, UDC ARTICLE 5.6 AIRPORT ENVIRONS ZONE (AEZ).” 7. COMMENT: 2-06.4.7.A.6.a – Demonstrate on the plan that the requirements of UDC Article 5.6.11 are met. 2-06.4.7.A.8 - For development package documents provide: 8. COMMENT: 2-06.4.7.A.8.a – There appears to be a discrepancy between the square footage listed under General Notes and what is shown within the footprint of the buildings. Under “EXIS. BLDG’S” “BLDG, ‘B’ you show 6,967 SF and if you subtract the 967 SF shown under “DEMOLITION” the remainder is 6,000 SF not 6,253 as shown within the footprint. 9. COMMENT: 2-06.4.7.A.8.a – Provide the square footage of the shed shown on the plan. 10. COMMENT: 2-06.4.7.A.8.a – Based on 2020 aerial photos there are several storage containers on site. If they are still on site show them on the plan and account for the square footage in all calculations. 11. COMMENT: 2-06.4.7.A.8.c – Provide a building expansion calculation on the plan. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 12. COMMENT: 2-06.4.9.E – As this site is made up of four (4) parcels, 132-25-0490, 132-25-0500, 132-25-051A & 132-25-051B, a lot combination is required, Provide a copy of the approved Pima County lot combo request with your next submittal. 13. COMMENT: 2-06.4.9.H.5.a – The shed shown on the plan along with any remaining storage containers square footage shall be included in the vehicle parking space calculation. Also clarify what the canopy is used for if it is part of the manufacturing it shall also be included in the calculation. 14. COMMENT: 2-06.4.9.H.5.a – The square footage listed under “PARKING”, 23,276 does not match up with the number under “NEW TOTAL BLDG sf 23,065 or the total if you add up the square footage listed within the footprint of the buildings, 21,318 15. COMMENT: 2-06.4.9.H.5.c – The loading space calculation is not correct. Per UDC TABLE 7.5.5-A: REQUIRED LOADING AREAS, Industrial Use Group (Section 11.3.5), ALL USES: Less than 25,000 sq. ft. GFA 0 Spaces are required. 16. COMMENT: 2-06.4.9.H.5.d – Clearly show the propose short- & long-term bicycle parking on the plan. Provide a detail for the required long-term bicycle parking that demonstrates how the requirements of UDC Articles 7.4.9.B & D are met. As you are proposing short term bicycle parking demonstrate on the provided detail or plan how the requirements of UDC Articles 7.4.9.B.1.e & g, 7.4.9.B.2.a & .h and 7.4.9.C.2.a are met. 17. COMMENT: 2-06.4.9.O – The street perimeter yard setbacks are incorrect. This site does not qualify for developing area setbacks therefore is required to meet the requirements of UDC Article 6.4.5.C.1.a 20’ or 1-1/2 times the height of the building. Based on the building height provided 27’-6” the required street perimeter yard is 41’-3”. 18. COMMENT: 2-06.4.9.Q – Provide the height of each building within the footprint. If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 06/11/2021 | AWARNER1 | LANDSCAPE | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Planning and Development Services Department, Plans Coordination FROM: Anne Warner, PLA PDSD Landscape/Native Plant Preservation Section PROJECT: Maddock Machinery Expansion ACTIVITY NO: DP21-0115 Address: 4793 S Julian Ave Parcel: Zoning: I-1 Existing Use: Industrial, General manufacturing Proposed Use: General manufacturing TRANSMITTAL DATE: June 11, 2021 DUE DATE: June 7, 2021 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Landscape Review Section comments were addressed. This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting. 1. UDC 2-10.4.1 Identification and Descriptive Data A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. The development package will contain the following identification in the lower right corner of each sheet: Any relevant case numbers for reviews or modifications that affect the site. Provide Case # on each sheet. Ensure that Zoning and Engineering comments are addressed prior to landscape section approval. 2. Provide verifiable site calculations to determine whether the expansion is less or greater than a 25% expansion of the site. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package If you have any questions, please contact me at anne.warner@tucsonaz.gov |
| 06/16/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Provide enclosures for the solid waste storage and collection location. 2. Show existing and proposed drainage patterns. Show roof drainage patterns. Demonstrate sidewalks will be kept flood free for up to a 10-year event. Loren Makus, EIT loren.makus@tucsonaz.gov |
| 06/18/2021 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email from: COTDSDPermits To: Philip Veneziano Fri 6/18/2021 10:07 AM Returned for Corrections Notice PERMIT/ACTIVITY: DP21-0115 DESCRIPTION: SITE: Maddock Machinery. Building demolition and addition. 4793 S JULIAN AV FEES DUE: $ 511.50 Please pay at a minimum, the REVIEW Fees. A payment is required before your next submittal. Thank you. ONLINE PAYMENT If amount isn't correct, check back in a few hours after it is updated. https://www.tucsonaz.gov/pdsd/fees 1- Click on: Pay Planning & Permit Fees 2- Enter your Permit Nbr, example: dp20-0000 (not case-sensitive but a hyphen-dash- is needed) 3- Business/Individual Name: Leave blank 4- Click "Continue" 5- Pay column - check the boxes 6- Click "Continue" INCLUDE IN YOUR RESUBMITTAL 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff Please title your 2nd submittal documents according to this example: 2_Comment Response Letter, 01.01.21 FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp (Select "Existing Application", then enter the permit number) SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab and you will see different sections - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW Sharon Beasley, Permit Specialist City of Tucson, Planning and Development Services Email for Development Pkgs: COTDSDpermits@TucsonAz.gov (disregard the email response that will be sent automatically) Email for Building Permits: PDSDinquiries@TucsonAz.gov |