Permit Number: DP21-0069
Parcel: 11918040C

Address:
3410 S 16TH AV

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP21-0069
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2021 SBEASLE1 START PLANS SUBMITTED Completed
03/26/2021 SBEASLE1 ENGINEERING REVIEW Passed Engineering passed during the OK to Submit.
03/31/2021 JPEELDA1 FIRE REVIEW Approved
04/13/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. An approved development plan is not to be used for construction or modification of on-site utilities (e.g. water service to buildings, building sewers, site lighting, electrical service to buildings, etc.). The construction of the on-site utilities may be included with the permit for constructing the building or as a separate permit. Remove any notes relating to how the site utilities are to be constructed.
2. Pima County Wastewater Reclamation Detail RWRD 401 (HCS) requires the installation of a 4” riser and cleanout to grade 12” from the property line (i.e. prior to entering the right of way).
3. The cleanouts for the building sewer shall open to allow cleaning in the direction of flow (see the two cleanouts located near the proposed Building C restroom). Reference: Sections 708.1.1 and 708.1.8, IPC 2018.
04/21/2021 STEVE SHIELDS ZONING REVIEW Passed
04/21/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Ricardo Enriquez
Wed 4/21/2021 11:15 AM

RETURNED FOR CORRECTIONS

PERMIT/ACTIVITY: DP21-0069
DESCRIPTION: SITE - Senor de Los Milagros. 3410 S 16TH AV

FEES DUE: $ 346.50
Please pay the total fees (or at a minimum, the REVIEW Fees). A payment is required before your next submittal. Thank you.

ONLINE PAYMENT
https://www.tucsonaz.gov/pdsd/fees
If amount isn't correct, check back in a few hours after data is updated.
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click Continue
5- Under the Pay column, check the boxes
6- Click Continue

RESUBMITTAL - FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)
1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Title your 2nd submittal documents according to this example:
2_Comment Response Letter, 01.01.21

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

Sharon Beasley
Permit Specialist

City of Tucson, Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
(Disregard any automatic reply you might receive)