Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: DP20-0272
Parcel: 105102450

Address:
565 E WETMORE RD

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP20-0272
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Correct the project description in the drainage statement.
01/04/2021 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Section Manager

PROJECT: 565 E Wetmore – New Drive Through
Development Package (1st Review)
DP20-0272

TRANSMITTAL DATE: January 4, 2021

DUE DATE: OK to Submit

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is December 30, 2021.

CONTENT REQUIREMENTS

1. 2-06.4.3 – Provide the development package case number, DP20-0272 , adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2-06.4.7.A.8 - For development package documents provide:

2. 2-06.4.7.A.8.c – As this is not a stand-alone use the building/use expansion calculation should be based on the entire shopping center.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

3. 2-06.4.9.H.5 – Demonstrate that the requirements of UDC Article 7.4.6.F.2.a.(2) are met.

4. 2-06.4.9.H.5.a - As this is not a stand-alone use the vehicle parking calculation should be based on the entire shopping center.

5. 2-06.4.9.H.5.a – The required sign mounting height shown on detail “C” sheet 4 should be 7’-0” to the bottom of the van accessible sign.

6. 2-06.4.9.R – As the angled vehicle parking shown along the east side of the building are allowed to overhang the sidewalk show the 2’-6” overhang on the plan and clearly demonstrate that a 4’ wide sidewalk is provided between the proposed outdoor patio and the vehicle overhang.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
01/05/2021 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Passed
12/31/2020 SBEASLE1 START PLANS SUBMITTED Completed