Permit Review Detail
Review Status: Completed
Review Details: DEV PKG - RESUBMITTAL
Permit Number - DP20-0252
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/15/2021 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 04/29/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. |
| 05/05/2021 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 05/05/2021 | SSHIELD1 | ADA | REVIEW | Passed | |
| 05/13/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 05/14/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | 1. Sheet 1 - Grading and Drainage Notes mentions an approved Grading and Drainage plan. Please clarify if the intention is to have this DP plan set to be reviewed as a grading/drainage plan or there is going to be a separate submittal of the grading plan. 2. Seeing inconsitencies between the DP plan set and the associated CM (T21CM01719) for building 2. One is showing on the west side of the building a new concrete walkway and the other shows it as dirt with concrete splash blocks under the downspouts. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 05/17/2021 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email sent from: COTDSDPermits To; Ricardo Enriquez Mon 5/17/2021 10:35 AM Returned for Corrections Notice PERMIT/ACTIVITY: DP20-0252 DESCRIPTION: SITE: Pascua Yaqui Tribe - ramps, curbs, pavers. 785 W SAHUARO ST FEE BALANCE: $0 (zero) Thank you for the payment. INCLUDE IN YOUR RESUBMITTAL 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff Please title your 3rd submittal documents according to this example: 3_Comment Response Letter, 01.01.21 FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp (Select "Existing Application", then the permit number) SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews - click on Review Details - Documents - click on “View” Sharon Beasley, Permit Specialist City of Tucson, Planning and Development Services Email for Development Pkgs: COTDSDpermits@TucsonAz.gov Email for Building Permits: PDSDinquiries@TucsonAz.gov |