Permit Number: DP20-0237
Parcel: 14027042C

Address:
2622 E BILBY RD

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP20-0237
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2021 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL
TO: Development Services Department
Plans Coordination Office
FROM: Nicholas Martell, Planner
PDSD Zoning Review Section
PROJECT: Industrial Building Site
Development Package (1st Review)
DP20-0237
TRANSMITTAL DATE: 1/14/2021
DUE DATE: 1/14/22
COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.
This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).
The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az
This link will take you directly to the section used for the standards review. The UDC & TSM requirements are in the Unified Development Code and can be viewed at the same web link as above
Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is , 2019.
SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section
2-06.1.0 GENERAL
2-06.2.0 APPLICATION SUBMITTAL REQUIREMENTS
2-06.3.0 FORMAT REQUIREMENTS
2-06.4.0 CONTENT REQUIREMENTS
2-06.5.0 FLEXIBLE LOT DEVELOPMENT (FLD) - ADDITIONAL REQUIREMENTS
2-06.1.0 GENERAL
2-06.1.1 PURPOSE
This standard has been prepared for the purpose of informing applicants of the submittal and review requirements for development package documents to assure proper and adequate information is presented in a consistent manner, thereby providing the basis for an efficient and timely review. The development package documents are prepared in support of applications for building permits and related reviews.
The information that is requested establishes the basis upon which the project will be approved and could affect what is required of the property in the future, should there be a proposal for expansion or for a different use of the property.
This standard does not waive any applicable city regulations or codes.
2-06.1.2 APPICABILITY
This standard shall be used for all site plans and tentative plats submitted to PDSD for review.
2-06.2.1 APPLICATION SUBMITTAL REQUIREMENTS
Development Package applications are available from PDSD. Completed applications and accompanying materials shall be submitted to PDSD. Incomplete or inaccurate applications will not be accepted, nor will any application in which the pre-application conference or neighborhood meeting requirements have not been met. The types of documents and the specific number of copies required of each of the documents are on the PDSD website or may be obtained from PDSD. Resubmittals of development packages require a comment response letter that details how all previous comments have been addressed. Provide the same number of copies of the comment response letter as plans provided.
The following documents and information shall be submitted upon application:
2-06.2.1 Application Form
A completed application signed by the property owner or authorized designee;
2-06.2.2 Development Package
A development package must be prepared to the format and content requirements described herein;
2-06.2.3 Related Reviews
In addition to the plan process, a project may require review for other types of plans and documents. The applications for those processes are submitted to the appropriate department for review and approval. These related reviews can be applied for so that review can occur concurrently with the development package application. However, it must be understood that, should the related application be approved subject to conditions or denied, this may affect the;
2-06.2.4 Concurrent Reviews
The development package is designed to allow for concurrent review of any site related reviews. Concurrent review means that all plans and documents needed for the review are submitted as one package. Examples of site related reviews include but are not limited to: site plans, landscape plans, NPPO plans, water harvesting plans, grading plans, SWPPP plans, floodplain use permits, and overlay reviews. Separate applications are often required for the different site related reviews even if the plans are submitted concurrently; and,
2-06.2.5 Fees
Fees in accordance with Section 4-01.0.0, Development Review Fee Schedule.
2-06.4.1 - Provide the email addresses of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package 18.
COMMENT: Provide the assigned development package case number, DP20-0237, adjacent to the title block on each sheet.
2-06.4.7.E.1.a 2 - Add as a note: "A project Construction Permit must be secured from Pima County Wastewater Management before beginning any work on this project."
2-06.4.9.E - Zoning cannot approve the Development Package without reviewing the lot line adjustment, and without the provided recordation information.
2-06.4.9.H.5 - The parking spaces on the west side of the building appear to not have sufficient back-out space, and would encroach into the neighboring parcel. Show the dimensions having sufficient space, or complete cross-access agreement with the owner of the parcel to the west.
If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
CDRC TRANSMITTAL
01/26/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change 1.The Project site lies within a critical basin, show compliance with critical basin detention and 5-yr retention.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
01/27/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: January 27, 2021
Returned for Corrections / Request for Resubmittal

PERMIT/ACTIVITY: DP20-0237
DESCRIPTION: Site/Grading/Swpp - Industrial Building at Bilby, 2622 E BILBY RD

FEES DUE: $ 3,073.40
Please pay the total fees (or at a minimum, the REVIEW Fees). A payment is required before your resubmittal.

ONLINE PAYMENT
https://www.tucsonaz.gov/pdsd/fees

PLEASE READ: If information is not available or amount isn't correct, check back in a few hours after data is updated.

(Visa, MC, Discover, American Express, or pay from bank account)
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info
7- If any issues, try using the browser Internet Explorer

RESUBMITTAL OF UPDATED/CORRECTED DOCUMENTS
Submit documents to NEW FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application", then the permit number

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

FYI - For all NEW development package submittals in the future (not resubmittals) on the Filedrop page, select the box: "SITE REVIEW...".

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
11/19/2020 SBEASLE1 START PLANS SUBMITTED Completed
12/15/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Water suppliers are required to protect their water systems from contamination by both Federal and State laws. To that end, each water service shall be equipped with a backflow prevention assembly. Installing stub-outs upstream of the backflow prevention assembly as described in keynote 20 of sheet 4 of 20 will necessitate the installation of a backflow assembly for each stub-out. Reference: City Ordinance #9976, https://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
2. Cleanouts for the building sewer shall not be located greater than 100-feet apart, measured along the developed pipe length from the upstream entrance of the cleanout. Revise item 5 of the Private Sewer Notes on sheet 4 of 20 to clarify that the maximum distance between cleanouts is based on the developed pipe length, not the horizontal distance. Reference: Section 708.1.1, IPC 2018.
12/18/2020 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

4.1 Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package will contain the following identification in the lower right corner of each sheet:

Any other relevant case number for reviews or modifications that affect the site.

Add case number and DP20-0237 on each sheet.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

Additional comment may apply
12/18/2020 GDAURIA1 FIRE REVIEW Reqs Change * ESFR sprinklers or smoke removal provisions required.
* Requires 26' aerial ladder access per IFC D105.
* Fire Dept. access doors required every 125' around building (if high-piled storage).
* Verify hyda=rants w/in 600. of all exterior portions of building.
* FDC required to be w/in 100' of a hydrant (if high-piled storage).