Permit Number: DP20-0232
Parcel: 14036005F

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Permit Number - DP20-0232
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2021 ALEXANDRA HINES ZONING REVIEW Reqs Change 1. Provide "DP20-0232" on bottom right-hand corner of all sheets.
2. Provide Covenants, Conditions, and Restrictions (CC&Rs) regarding the homeowner's association's responsibility for the ownership and maintenance of commonly-owned property.
3. Provide general note regarding mailboxes. Gang location or at each lot? If gang location, showcase on plan with pedestrian access.
4. Provide approved letter advising whether the design conforms to the standards established by the DRC per PAD-21 Section III M.

Alexandra Hines
alexandra.hines@tucsonaz.gov

Alexandra Hines
01/29/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. A Pima County Regional Flood Control District Facility Impact Permit is required for the improvements affecting Julian Wash. Provide a copy of the approve FIP before this DP is issued.
2. Clearly show how water harvesting will be maximized.
02/01/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: February 1, 2021
Returned for Corrections / Request for Resubmittal

PERMIT/ACTIVITY: DP20-0232
DESCRIPTION: Tentative Plat/Floodplain - Valencia Crossing, Lots 1-161 and common areas A-1, A-2, B-1, B-2, and C-1.

FEES DUE: $ 16,168.55 (see image in email below)
Please pay the total fees (or at a minimum, the REVIEW Fees). A payment is required before your resubmittal.

ONLINE PAYMENT
https://www.tucsonaz.gov/pdsd/fees

PLEASE READ: If information is not available or amount isn't correct, check back in a few hours after data is updated.

(Visa, MC, Discover, American Express, or pay from bank account)
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click the blue tab: Continue
5- Under the Pay column, check the boxes you want to pay
6- Click Continue, then enter your credit card info
7- If any issues, try using the browser Internet Explorer

RESUBMITTAL OF UPDATED/CORRECTED DOCUMENTS
Submit documents to NEW FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application", then the permit number

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

FYI - For all NEW development package submittals in the future (not resubmittals) on the Filedrop page, select the box: "SITE REVIEW...".

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
11/19/2020 SBEASLE1 UTILITIES SOUTHWEST GAS Passed
11/19/2020 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed
11/19/2020 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
11/24/2020 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved 11/24/20
ADOT South Central District would like to advise the Developer and Engineer for Valencia Crossing, of ADOT's Interstate 10 & State Route 210 corridor study. This may or may not have an impact on the future of this Development. Study can be found at the link below.
https://azdot.gov/node/14424

This information is provided so an informed decision can be made for all parties; as ADOT looks for future improvements in the interstate corridor.

Richard La Pierre
Permits Supervisor, South Central District
1221 South Second Avenue
Tucson, Arizona 85713
520.388.4234 (office), 520.307.5893 (cell)
12/01/2020 GDAURIA1 COT NON-DSD FIRE Completed * Verify that hydrants are within 400' of all exterior portions of any future structures (600' if sprinklered).
12/09/2020 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved 12/09/20

No existing or proposed Tucson Parks and Recreation facilities are affected by this development.

Howard B. Dutt, RLA, Landscape Architect
Tucson Parks and Recreation
(520) 837-8040
12/10/2020 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Approved December 9, 2020

RE: DP20-0232 Tentative Plat/Floodplain - Valencia Crossing, Lots 1-161 and common areas A-1, A-2, B-1, B-2, and C-1, Received November 19, 2020

Thank you for the opportunity to comment on DP20-0232, Valencia Crossing, Lots 1-161; 1st Submittal, a development package application for an approximately 37 acre site, located northwest of the intersection of East Littletown Road and East Valencia Road. The property is zoned Planned Area Development 21 (PAD-21), with the proposed development being a single family residential development.

This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.

The Tucson Airport Authority (TAA) approves the 1st submittal of this project.

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.

Respectfully,
Scott Robidoux, C.M., Senior Airport Planner
12/10/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Assuming a FFE that is 0.67 feet higher than the pad elevation, lot 84 does not appear to require a backwater valve (Manhole #16 rim, 2670.08'; FFE 2671.17'). Reference: Section 714.1, IPC 2018.
12/14/2020 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved 12/14/20
Tucson Electric Power Co., (TEP) has reviewed and approves the Development Plan/Tentative Plat for Valencia Crossing Lots 1-161. A preliminary electrical drawing will be prepared when all required project information requested per email to Rick Engineering on December 14, 2020, is provided. Easements for TEP facilities must be shown on the final plat prior to TEP’s approval.

If there are any questions, please contact me at 520-401-9895.

Thank you,
Mary Burke, Senior Right of Way Agent

Tucson Electric Power Co.
Land Resources – RC 131
3950 E. Irvington Road, Tucson, AZ 85714-2114
Cell - 520-401-9895, mburke@tep.com
12/15/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
12/16/2020 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

4.1 Identification and Descriptive Data

All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package will contain the following identification in the lower right corner of each sheet:

Any other relevant case number for reviews or modifications that affect the site.

Page Break


Add case number and DP20-0231 on each sheet.

Indicate graphically, where possible, compliance with conditions of PAD-21document.

https://www.tucsonaz.gov/files/pdsd/pdfs/PlannedAreaDevelopmentAndOverlay/C9-12-03_Valencia_Crossing_PAD.pdf Page 49 Section D

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.

Additional comment may apply
12/24/2020 SBEASLE1 PIMA COUNTY ADDRESSING Reqs Change (The ATTACHED PDF mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.)

12/24/20
Valencia Crossing, DP20-0232, 1st submittal is being Returned for Corrections by Pima County Addressing. The attached pdf contains Addressing’s comments.

Please let me know if you have any questions.

Thank you,
Robin Freiman, Addressing Official

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570
12/28/2020 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Completed
12/28/2020 SBEASLE1 START PLANS SUBMITTED Completed