Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP20-0231
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2021 | SBEASLE1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Reqs Change | (The ATTACHED PDF mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.) 01/21/21 DP20-0231, Copperstate OBGyn, 1st submittal, is being Returned for Corrections by Pima County Addressing. The attached pdf contains Addressing’s comments. Please let me know if you have any questions. Thank you, Robin Freiman, Addressing Official Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-7570 |
| 01/06/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/22/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Provide distance and bearing for all property boundaries. 2. Show bollards protecting the walls of the trash enclosure in Detail 12. 3. Show how water harvesting is maximized. 4. Show how the open courtyard will drain rainwater |
| 01/25/2021 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | DATE: January 25, 2021 Returned for Corrections / Request for Resubmittal PERMIT/ACTIVITY: DP20-0231 DESCRIPTION: SITE - Copperstate OBGyn, building addition, 5550 E HAMPTON ST FEE BALANCE: $0 (zero) Thank you for the payment. RESUBMITTAL OF UPDATED/CORRECTED DOCUMENTS Submit documents to NEW FILEDROP: https://docs.tucsonaz.gov/Forms/tucsonpermitapp Select "Existing Application", then the permit number 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff - Title the documents for your 2nd submittal starting with the submittal number, for example: 2_Plan_Set SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews - click on Review Details - Documents - click on View to the right of each document FYI - For all NEW development package submittals in the future (not resubmittals) on the Filedrop page, select the box: "SITE REVIEW...". Thank you. City of Tucson Attn: Sharon Beasley, Permit Specialist Planning and Development Services email: COTDSDPermits@TucsonAz.gov |
| 11/19/2020 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 12/01/2020 | GDAURIA1 | FIRE | REVIEW | Reqs Change | * A hydrant must be located within 400' of any outside portion of the building (600' if sprinklered and fire underground shown on DP). |
| 12/10/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the site drawing to include the following existing utility information: a. The pipe diameter of the sanitary sewer, the invert and rim elevation of all manholes and the Pima County Wastewater Management Department (PCWMD) reference number. b. The point of connection to the existing public sewer. c. The first floor elevation for the building Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018. |
| 12/16/2020 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | ADMINISTRATIVE MANUAL 4.1 Identification and Descriptive Data All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. The Development Package will contain the following identification in the lower right corner of each sheet: Any other relevant case number for reviews or modifications that affect the site. Add case number and DP20-0231 on each sheet. APPLICABILITY The provisions of this section apply to the following: A. All new development ; and, B. Expansion of existing development , as provided below: 1. Buildings Greater Than 10,000 Square Feet On sites where the gross floor area of the existing building (s) is more than 10,000 square feet, expansion in square footage of land area, floor area , lot coverage , or vehicular use area as follows: a. If the expansion is less than 25%, the standards of this section apply only to the proposed expansion. Existing development on the site is subject to the zoning standards in effect at the time the existing development received zoning approval. b. If the expansion is 25% or greater or if expansions as of February 15, 1991, cumulatively result in a 25% or greater expansion in land area, floor area , lot coverage , or vehicular use area , the standards of this section apply to the entire site . Street Landscape Border Minimum Width Street landscape borders must be a minimum of ten feet wide as measured from the streetproperty line . On streets designated as Major Streets and Routes (MS&R), the street landscape border must be measured from the future MS&R right-of-way line as determined by Section 5.4.4, Establishment of MS&R Right-of-Way Lines and Gateway Routes. Some of the landscape borders along Hampton street are not 10’. Provide the required landscape border width or Design Development Option may be necessary. Ensure that Zoning and Engineering comments are addressed prior to landscape section approval. Additional comments may apply |