Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP20-0201
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/12/2020 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 10/22/2020 | GDAURIA1 | FIRE | REVIEW | Completed | |
| 11/05/2020 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | ADMINISTRATIVE MANUAL 4.1 Identification and Descriptive Data The Development Package will contain the following identification in the lower right corner of each sheet: Any relevant case numbers for reviews or modifications that affect the site Provide Case # DP20-0201 on each sheet. If funded by the State of Arizona and a verification letter is granted, then Zoning requirements are not applicable. Additional comments may apply. |
| 11/09/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The rim elevation of the next upstream sanitary manhole (3105-01, 2753.40') is higher than the first-floor elevation (2752.16). Note that a backwater valve will be required per Section 714.1, IPC 2018, as amended by the City of Tucson |
| 11/19/2020 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Section Manager PROJECT: LTS Tucson Campus 2021 Development Package (1st Review) DP20-0201 TRANSMITTAL DATE: November 19, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is October 06, 2021. 1. COMMENT: Until a site plan has been submitted and approved Zoning cannot approve the grading plan. 2. COMMENT: Clarify if this is a State Charted school and if so submit documentation to the COT PDSD Zoning Administrator for review. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 12/08/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | DP20-0201 This review assumes the proposed use is a charter school. If this is not a charter school, provide a complete development package meeting site plan requirements. 1. Improvements in the right-of-way, including the Rolling Hills Wash, will require a ROW use permit or private improvement agreement from the City of Tucson Department of Transportation and Mobility. https://www.tucsonaz.gov/tdot/permits-and-codes-section 2. The Floodplain Use Permit must be issued along with this permit. T20OT00802. The review fees must also be paid. 3. The Rolling Hills Wash adjacent to the site has concrete banks. Provide justification for conversion to gabions. 4. General notes 11, 13, 14, 19, and 21 on sheet one do not seem to apply or require revision. Please let me know when the plans have been submitted so I can complete a virtual "over-the-counter" review. |
| 12/09/2020 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | DATE: December 9, 2020 RETURNED FOR CORRECTIONS NOTICE Your Next Steps: 1. Payment 2. Resubmittal of updated/corrected documents IMPORTANT - NEW FILEDROP: https://docs.tucsonaz.gov/Forms/tucsonpermitapp Select "Existing Application" FYI - For all NEW submittals (not this resubmittal) on the new Filedrop page, select the box: "SITE REVIEW..." so it is routed to correct staff member for quicker processing. PERMIT/ACTIVITY: DP20-0201 DESCRIPTION: Grading/SWPPP/Floodplain - LTS Tucson Campus 2021, Legacy Traditional School (charter) FEES DUE: $ 2,816.96 Please pay the total fees (or at a minimum, the REVIEW Fees). A payment is required before your next submittal. ONLINE PAYMENTS https://www.tucsonaz.gov/pdsd/fees IMPORTANT: If information is not available or amount isn't correct, check back later after data is updated. (Visa, MC, Discover, American Express, or pay from bank account) 1- Click on: Pay Planning & Permit Fees 2- Enter your Permit Nbr, example: dp20-0000 (not case-sensitive but a hyphen-dash- is needed) 3- Business/Individual Name: Leave blank 4- Click the blue tab: Continue 5- Under the Pay column, check the boxes you want to pay 6- Click Continue, then enter your credit card info 7- If any issues, try using the browser Internet Explorer SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews - click on Review Details - Documents - click on View to the right of each document YOUR NEXT STEP: Submit documents to NEW FILEDROP: https://docs.tucsonaz.gov/Forms/tucsonpermitapp 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff - Title the documents for your 2nd submittal starting with the submittal number, for example: 2_Plan_Set Thank you. City of Tucson Attn: Sharon Beasley, Permit Specialist Planning and Development Services email: COTDSDPermits@TucsonAz.gov |