Permit Number: DP20-0166
Parcel: 141210270

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP20-0166
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2021 ELISA HAMBLIN ZONING REVIEW Approved
01/15/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. The predevelopment 100-year floodplain as shown in Figure 4 of the Drainage Report (DR) (Sheet 13 of 53) must be the basis for determining the Regulated Area (RA) and the Protected Riparian Area (PRA) in the Environmental Resource Report (ERR).
2. The RA and PRA must be delineated within all submitted plans and documents.
3. Demonstrate in the DR, ERR and Development Plan there will be no unnecessary disturbance of riparian resources. (TS 4-02.2.B.2)
4. Revise the DR to show location of water harvesting areas (WHA)providing retention volume. Show how the runoff directed to the WHA will meet the volume requirements.
5. Ensure slopes on grading plan for drainage areas and WHA meet the volume requirements.
6. Show proposed elevations and necessary eyebrows or other features to provide required effective volumes.

Loren Makus EIT
Senior Engineering Associate
loren.makus@tucsonaz.gov
01/18/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Date: Jan. 18, 2021

Returned for Corrections / Request for Resubmittal
PERMIT/ACTIVITY: DP20-0166

DESCRIPTION: SITE/GRADING/FLOODPLAIN : RV Storage - Tucson.

FEE BALANCE: $0 (zero) Thank you for the payment.

RESUBMITTAL OF UPDATED/CORRECTED DOCUMENTS
Submit documents to NEW FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 3rd submittal starting with the
submittal number, for example: 3_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

FYI - For all NEW development package submittals in the future (not resubmittals) on the Filedrop page, select the box: "SITE REVIEW...".

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov
11/11/2020 SBEASLE1 START PLANS SUBMITTED Completed
11/12/2020 GDAURIA1 FIRE REVIEW Completed
12/08/2020 ANDREW CONNOR LANDSCAPE REVIEW Approved