Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP20-0078
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/13/2020 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 05/01/2020 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | ADMINISTRATIVE MANUAL SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS 4.1 Identification and Descriptive Data The development package will contain the following identification in the lower right corner of each sheet: Any relevant case numbers for reviews or modifications that affect the site. Provide Case # DP20-0078 on each sheet. Ensure that Zoning and Engineering comments are addressed prior to landscape section approval. Additional comments may apply |
| 05/06/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Floodplain use permit is required. 2. Provide for inspection and maintenance of the fence within the channel to prevent blockage. |
| 05/11/2020 | ELISA HAMBLIN | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Elisa Hamblin, AICP; Principal Planner PROJECT: Pima Air and Space Museum, New Fence/Wall Development Package (1st Review) DP19-0078 TRANSMITTAL DATE: May 11, 2020 DUE DATE: May 11, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is April 8, 2021. 1. 2-06.3.10 - A legend that shows and describes all symbols used on the drawing is to be provided, preferably on the first sheet. 2. 2-06.4.2.B – Provide in the title block a brief legal description. 3. 2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. As a portion of a larger site, the existing use is Cultural Use. 4. 2-06.4.7.A.6.a – Include development package case number DP20-0078 adjacent to the title block on all sheets. 5. 2-06.4.7.A.6.a – Add a general note that this site is subject to the Airport Environs Zone and is intended to comply with the standards of that overlay. 6. 2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. 7. 2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. 8. Clarify General Note 11. This note appears to be language that typically appears as a rezoning condition, but I don’t see how it applies to this site. Please provide additional information. The proposed fencing does not appear to meet the requirements of this note. If you have any questions about this transmittal, please contact me at Elisa.Hamblin@tucsonaz.gov or (520) 837-4966. As the comments in this transmittal are minor, after a resubmittal is received an over-the-counter review can be scheduled. Please contact me directly. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 05/12/2020 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | RETURNED FOR CORRECTIONS NOTICE Your Next Steps: 1. Payment 2. Resubmittal of documents DESCRIPTION: SITE/FLOODPLAIN - Pima Air & Space Museum, perimeter fence installation, east parcel. PERMIT/ACTIVITY: DP20-0078 FEES DUE: $ 99.00 Please pay the total fees (or Review Fees at a minimum). A payment is required before the next submittal. ONLIINE PAYMENT https://www.tucsonaz.gov/pdsd/online-resources-fees-maps-records 1. NOTE: It may take 1-2 days for complete information to be viewable 2. Visa, MC, Discover, American Express or pay by checking account 3. Not case-sensitive but a hyphen is needed, for example: dp19-2000 4. Enter Permit Nbr 5. Business/Individual Name: Leave blank 6. Click the Continue tab 7. If any issues, try using the browser Internet Explorer SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews - click on Review Details - Documents - click on blue icon to the right of each document YOUR NEXT STEPS: Submit documents to the Filedrop https://www.tucsonaz.gov/file-upload-pdsd 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff - Name the 2nd submittal documents starting with the submittal number, for example: 2_Plan_Set NOTE: The City of Tucson's Permit Counter at 201 N. Stone Avenue (the physical office) is closed to the public until further notice. Our staff is working remotely. All communications are by telephone or email. CONTACT US Monday-Friday, 8:00 am to 12:00 noon https://www.tucsonaz.gov/pdsd/virtual-service-counter For information or an over-the-counter review, sign in to the Virtual Service Counter and we will give you a call. Thank you. Sharon Beasley, Permit Specialist City of Tucson Planning and Development Services email: COTDSDPermits@TucsonAz.gov |