Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP20-0076
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2020 SBEASLE1 START PLANS SUBMITTED Completed
05/26/2020 GDAURIA1 FIRE REVIEW Completed
05/29/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/02/2020 ANDREW CONNOR LANDSCAPE REVIEW Approved
06/09/2020 STEVE SHIELDS ZONING REVIEW Approved
06/16/2020 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP20-0076

1) The 1/12 water harvesting ratio provided, while sufficient for overall volume does not indicate which water sheds contribute to which basin. For example the narrow basin to the west is undersized given the tributary area that is feeding it. Provide a water shed boundary for each of the water harvesting basins showing that the tributary impervious area is being discharges into a basin that has sufficient capacity
2) Show how water flow to the west and north is controlled to match the existing discharge points and not affect surrounding property. This may require a curb or swale to accomplish
3) Provide additional spot grades showing the flow path of the water

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
06/17/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change RETURNED FOR CORRECTIONS NOTICE
Your Next Step: Resubmittal of documents

DESCRIPTION: SITE - Spring Triplex, 2545 E. Spring Street.
PERMIT/ACTIVITY: DP20-0076
FEE BALANCE: $0 (zero) Thank you for the payment.

SEE REVIEW COMMENTS and your submitted documents on PRO:
www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on blue icon to the right of each document

YOUR NEXT STEP: Submit documents to the Filedrop
https://www.tucsonaz.gov/file-upload-pdsd

FOR FASTER PROCESSING, on the Filedrop page, select the box
"Development Package or Land Division". This applies to all
DP submittals, DP resubmittals, and DP revisions - and all Land Splits.
(For Building Permits, continue to select "Resubmittals/Revisions...".)

1) Comment Response Letter
(your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name the 3rd submittal documents starting with the
submittal number, for example: 3_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2020 SBEASLE1 OUT TO CUSTOMER Completed