| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2020 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 01/02/2020 | SBEASLE1 | UTILITIES | SOUTHWEST GAS | Passed | Review not required. This agency was notified for their information only. |
| 01/02/2020 | SBEASLE1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | Review not required. This agency was notified for their information only. |
| 01/02/2020 | SBEASLE1 | OTHER AGENCIES | U. S. POST OFFICE | Passed | Review not required. This agency was notified for their information only. |
| 01/22/2020 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: David Rivera PDSD Zoning Review Section PROJECT: Cherrybell Medical Center / Residential Care - Physical Behavioral Health Use Development Package (1st Review) Phase II - 1230 S. Cherrybell Stravenue DP19-0314 - C-2 Zoning per Rezoning Case C9-17-09 TRANSMITTAL DATE: January 22, 2020 DUE DATE: January 31, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is December 26, 2020. SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) CONTENT REQUIREMENTS 1. COMMENT: 2-06.4.3 - Provide the development package case number, DP19-0314, adjacent to the title block on each sheet. Clarify which address is correct for this building in Phase II, 1538 E 22nd Street or 1230 S. Cherrybell Stravenue. Revise the administrative address as required. 2. COMMENT: 2-06.4.8.C - Clarify if curb and sidewalk is to be required by TDOT along the 24th Street fronting the Phase II portion of this overall development. 3. COMMENT: 2-06.4.9.H.5.d - Demonstrate compliance for the long term bicycle facility as noted per UDC Article 7 section 7.4.9.D 4. COMMENT: 2-06.4.9.O - In order to verify if the building setback along the 24th Street frontage is met, the future curb location must be presented on the plan. Provide the building setback based on an ADT of 140 to 1,000. 5. COMMENT: 2-06.4.9.R - Clarify if the drop of area is to be provided with and accessible ramp or is the area flush with the curb? Bollards may be required with a minimum spacing of five feet from center if the drop pavement area is flush with the curb/walkway area. If an accessible is proposed draw and label the location(s). Draw and label the accessible route. Provide a pedestrian sidewalk connection to the refuse location from the building - TS 7-01.3.3.B. 6. COMMENT: 2-06.4.9.T - Demonstrate compliance for maneuverability in and out of the refuse location. 7. COMMENT: Clarify what is the purpose of the dog kennels along the east side of the new building? ***For additional information on the any standard presented in this memo, please refer to the City of Tucson "Unified Development Code" - Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations If you have any questions about this transmittal, Contact David Rivera on Tuesday, or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 01/22/2020 | DAVID RIVERA | ZONING HC | REVIEW | Reqs Change | See zoning comments. |
| 01/23/2020 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Reqs Change | January 23, 2020 ACTIVITY NUMBER: DP19-0314 PROJECT NAME: Cherry Bell Medical Center Phase II PROJECT ADDRESS: 1538 E 22nd Street PROJECT REVIEWER: Zelin Canchola TDOT Resubmittal Required: The following items must be revised and added to the Development plan. 1. Show new sidewalk along frontage of Cherry Bell SV and 24th Street, and two new ramps. One at the corner of 24th and Cherry Bell, and one at the end of sidewalk on 24th street where it curves onto Cherry Douglass. 2. Tie new sidewalk into existing ped ramp along Cherry Bell and continue sidewalk with curb along the frontage of 24th Street. At the end of sidewalk, on 24th street provide a ped ramp to ensure a pedestrian connection from across the street (Cherry Douglass) and 24th Street. If you have any questions, I can be reached at 520 837 6659 or zelin.canchola@tucsonaz.gov |
| 01/28/2020 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | Regional Traffic Engineering has no comments on this submittal and supports its approval. The proposed development location will have no impact to any ADOT facilities. Thank you. Tom Martinez ADOT TMartinez@Azdot.gov |
| 01/28/2020 | SBEASLE1 | COT NON-DSD | PARKS & RECREATION | Approved | No existing or proposed Tucson Parks and Recreation facilities are affected by this development. Howard B. Dutt, RLA Landscape Architect Tucson Parks & Recreation, (520) 837-8040 Howard.Dutt@tucsonaz.gov |
| 01/29/2020 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | ADMINISTRATIVE MANUAL SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS 4.1 Identification and Descriptive Data All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. The Development Package will contain the following identification in the lower right corner of each sheet: Any relevant case numbers for reviews or modifications that affect the site. Add Case # DP19- 0314 Indicate graphically, where possible, compliance with conditions of rezoning. Ensure that all Zoning and Engineering comments and concerns are addressed. Additional comments may apply |
| 01/29/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 01/30/2020 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Approved | |
| 01/31/2020 | SBEASLE1 | OTHER AGENCIES | TUCSON AIRPORT AUTHORITY | Reqs Change | January 31, 2020 RE: DP19-0314 / SITE/GRADING - Cherrybell Medical Center, Phase 2 (revision to DP17-0157), 1ST Submittal, Received January 2, 2020 Thank you for the opportunity to comment on DP19-0314, Cherrybell Medical Center, Phase 2 (revision to DP17-0157), 1ST Submittal, a development package application for an approximately 0.48 acre site, located southeast of the intersection of South Kino Parkway and East 22nd Street. The property is zoned Residence Zone 2 (R-2), Commercial Zone 3 (C-3), and Light Industrial Zone (I-1), with the proposed zoning being Commercial Zone 2 (C-2) and the proposed development being the second phase a medical outpatient (excluding blood donor centers) and residential care service (physical and behavioral health service). This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace. The Tucson Airport Authority conditionally approves the subject request contingent upon the following condition of approval, as noted below. This condition shall be identified in the general notes of the revised development plan. Condition of approval: 1. "According to the Federal Aviation Administration (FAA) Notice Criteria Tool, this project area is located in proximity to a navigation facility and could impact navigation signal reception. As the project site develops, every project applicant shall file FAA Form 7460 with the FAA at least 45 days before construction activities begin unless FAA staff, with the Obstruction Evaluation / Airport Airspace Analysis (OE/AAA), provides the project applicant with written communication that filing FAA Form 7460 is not required. It is highly recommended that the applicant file earlier than 45 days to provide the applicant with sufficient time to respond to any concerns which are identified by the FAA. Any cranes which are used must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp" Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811. Respectfully, Scott Robidoux, , Senior Airport Planner cc: Lisa Bowers |
| 02/03/2020 | MARTIN BROWN | COT NON-DSD | FIRE | Approved | |
| 02/04/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Show maneuverability for the solid waste service truck exiting after servicing the new enclosure locations. The backup distance seems to exceed the 80-foot maximum. 2. Provide dimensions from the end of the backup spur. Three feet are required from the face of curb to the fence or wall. |
| 02/04/2020 | SBEASLE1 | UTILITIES | TUCSON ELECTRIC POWER | Approved | See TEP Approval Letter, TEP Utilities and Easements, and TEP Facilities Map (all dated 02.04.2020) in "Documents" section on PRO. |
| 02/05/2020 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | PLAN RETURNED FOR CORRECTIONS NOTICE Your Next Steps: A resubmittal which includes a Comment Response Letter DESCRIPTION: SITE/GRADING - Cherrybell Medical Center, Phase 2 (revision to DP17-0157). PERMIT: DP19-0314 Please include this number on all future correspondence and in Filedrop's "Project Description" field. PROJECT MANAGER: Samuel.Rogers@Tucsonaz.gov or 837-6932 FEE BALANCE: $0 (zero) VIEW REVIEWER'S COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, left side, Activity Search, enter the Activity Number - Permits section, click on blue tab - Documents section, click on blue icon to the right of each document - Reviews section, click on Review Details YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set) 3) Any other documents requested by review staff - Filedrop: In the Project Description field, enter the Activity/Permit Number - Name your 2nd submittal documents to start with the number, for example: 2_Plan_Set Thank you. Sharon Beasley, Permit Specialist City of Tucson Planning and Development Services Attn: Permit Counter/Payments 201 N. Stone Avenue, 2nd Floor Tucson, AZ 85701 email: COTDSDPermits@TucsonAz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2020 | SBEASLE1 | OUT TO CUSTOMER | Completed |