Permit Number: DP19-0257
Parcel: 11623108A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP19-0257
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2022 SBEASLE1 ENGINEERING REVIEW Reqs Change (The comments below were copied from the OK to Submit)

1. Show drainage openings in the proposed wall along Starr Pass Boulevard. Show how water harvesting will not be adversely impacted by the proposed wall and its foundation.
2. Show the height of the new parking canopies above the parking surface. If there is less than 15 feet of clearance, the edge of the canopy must be one foot from the end of the parking spaces.
3. In plan view, canopies are proposed in both the north and south parking areas. Revise the sections for both to show the proposed canopies. Clearly show the one-foot set-back from the end of the parking spaces, if applicable.
4. Show how canopy drainage will not be directed to the adjacent sidewalks.

Loren Makus
loren.makus@tucsonaz.gov
03/10/2022 SBEASLE1 ENGINEERING REVIEW Reqs Change Comment 5:
The new wall along Starr Pass is within the future sight visibility triangle. Remove the wall or obtain a TSMR.
03/23/2022 JPEELDA1 FIRE REVIEW Approved
03/23/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: 910 W Starr Pass Blvd
Development Package (1st Review Revision #1)
DP19-0257

TRANSMITTAL DATE: March 23, 2022

DUE DATE: March 30, 2022

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

1. COMMENT: 2-06.4.9.H.2 – Per TSM Section 10.01.5.1.A.1 the proposed 6’-0” high wall called out under Keynote 25 exceeds the allowed 30” height allowed within an SVT. See Engineering comments

2. COMMENT: 2-06.4.9.H.5 – Per UDC Article 7.4.6.F.2.2.a.(1) Access lanes and PAALs must be setback at least one foot from an open structure, such as a carport or covered pedestrian access path as measured from the closest part of the structure or roof overhang. Show the required 1’-0” setback from the PAAL to the shade structure on the plan.

3. COMMENT: 2-06.4.9.O – Per UDC Article 6.4.5.B.2 A vertical structural member(s) (i.e., post, column, dormer wall) supporting a roof extension from the principal structure is considered a wall for applying perimeter yard requirements. Clearly show the posts supporting the shade structures. Also, per UDC Article 6.4.5.D.1 the overhang from the post supporting the shade structure can only encroach into the required 10’-0” setback 2’-0”.

If you have any questions about this transmittal, please contact Nicholas Ross at Nocholas.Ross@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
04/07/2022 AWARNER1 LANDSCAPE REVIEW Approved
04/07/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
To: Dan White
cc: Robert Brakey-Campos
Thu 4/7/2022 4:25 PM

REVIEW NOTICE
REVISION Returned for Corrections: DP19-0257

DESCRIPTION: SITE/GRADING - 910 W. Starr Pass Blvd, Eight SFR rental units.

Fee Balance: $0 (zero) Thank you for the payment.

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab to see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. UPLOAD A RESUBMITTAL to Filedrop:
1) Comment Response Letter (your response to REQUIRES CHANGE comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- "Permit Number" field: enter the number (and any notes for our staff)
- Select "PLANS" for all documents

Thank you.
Sharon Beasley, Certified Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov