Permit Number: DP19-0175
Parcel: 12419040F

Address:
555 S CHERRY AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - DP19-0175
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2022 SBEASLE1 ENGINEERING REVIEW Reqs Change (Comments below are from the OK to Submit)

Show surface treatment for the graded pad where the retail building was deleted. UDC 7.6.4.E

Loren Makus
loren.makus@tucsonaz.gov
03/11/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Cherry Mixed Use Lofts
Development Package (Revision #2)
DP19-0175

TRANSMITTAL DATE: March 11, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

1. COMMENT: 2-06.4.9.U – As this change does not match the PDP submitted for the rezoning provide written documentation from John Beall, John.Beall@tucsonaz.gov, that confirms that a change to PDP is not required or if required that it has been completed.

2. COMMENT: 2-06.4.9.X - Demonstrate how dust control is provided for the pad area where the building was removed.

3. COMMENT: 2-06.4.9.X – The landscape plans will need to be revised to match the site & grading.

If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
03/14/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/21/2022 JPEELDA1 COT NON-DSD FIRE Reqs Change As there is a rezoning condition that calls for the DP to be in compliance with the PDP, which identified the commercial building in the northern part of the site, label this clouded area as "future building" or "future building 11" under the current DP, and keep the associated parking. Then come back at a future date with another DP for this future commercial building.

Sheet 1 includes a note stating that rezoning conditions are found on sheet 3 of the plan set, but sheet 3 along with several other sheets from later on in the plan set appear to be missing from the submittal. Include all plan sheets with the resubmittal.

Peter McLaughlin
PDSD Entitlements Section
03/21/2022 JPEELDA1 COT NON-DSD FIRE Reqs Change DP shows the removal of commercial building. Address does not show the fire alarm drawings/permit number, I belive that the FACP was going in the commercial building. If the FACP is being relocated, it shall not be in a tenant space. Please provide more information.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
04/06/2022 AWARNER1 LANDSCAPE REVIEW Needs Review Landscape plans need to be submitted for review.
04/07/2022 PETER MCLAUGHLIN COT NON-DSD COMMUNITY PLANNING Reqs Change As there is a rezoning condition that calls for the DP to be in compliance with the PDP, which identified the commercial building in the northern part of the site, label this clouded area as "future building" or "future building 11" under the current DP, and keep the associated parking. Then come back at a future date with another DP for this future commercial building.

Sheet 1 includes a note stating that rezoning conditions are found on sheet 3 of the plan set, but sheet 3 along with several other sheets from later on in the plan set appear to be missing from the submittal. Include all plan sheets with the resubmittal.

Peter McLaughlin
PDSD Entitlements Section
04/08/2022 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
To: Ryan Stucki
Fri 4/8/2022 11:45 AM

REVISION #2 REVIEW NOTICE
Returned for corrections, DP19-0175

DESCRIPTION: SITE/GRADING/SWPPP - Cherry mixed use lofts, Res & Commercial. 555 S CHERRY AV

REVISION #2 FEES DUE: $ 165.00
(extra two hours review time by Fire Dept)
** See Online Payment Instructions attached **

VIEW the review comments and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

YOUR NEXT STEPS: Submit documents to the Filedrop
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application"
1) Comment Response Letter (your response to
the reviewer's Requires changes comments)
2) Plan Set (or individual sheets)
3) Any other items/documents requested by review staff

Thank you.