Permit Number: DP19-0124
Parcel: 132160430

Address:
1350 E BENSON HY

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP19-0124
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2019 SBEASLE1 START PLANS SUBMITTED Completed
05/14/2019 SBEASLE1 WWM REVIEW Passed
05/15/2019 JOHN VAN WINKLE ENGINEERING REVIEW Denied 1) Site is located with a Balanced Basin as defined by the City of Tucson Stormwater Detention/Retention manual is subject to 5 year threshold retention and also detention to ensure that 2,10 and 100 year peak post development discharges do not exceed pre-developed conditions. As such A drainage report inkeeping with chapter 2 of the City of Tucson Standards Manual for Drainage Design and Floodplain Managment is required. A drainage report is required in order to intake the project for review.
2) Confirm that area of disturbance is only 0.86 acres. Proposed plan appears to disturb greater than 1 acre. If so, a SWPPP site plan and manual is required

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
05/16/2019 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Needs Review This project does require review by Pima County Addressing.
Thank you
Nicholas Jordan, Addressing Specialist
Pima County Development Services Department
201 N Stone AV
Tucson, AZ 85701
(520) 724-9623
05/16/2019 ALEXANDRA HINES ZONING REVIEW Needs Review