Permit Number: DP19-0034
Parcel: 132130780

Address:
1740 E 36TH ST

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP19-0034
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2020 SBEASLE1 START PLANS SUBMITTED Completed
04/10/2020 LOREN MAKUS ENGINEERING REVIEW Approved
04/13/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Section Manager

PROJECT: TEP Kino Substation
Development Package (2nd Revision)
DP19-0034

TRANSMITTAL DATE: April 13, 2020

DUE DATE: Revision #2 Ok to Submit.

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

2-06.4.0 CONTENT REQUIREMENTS

1. 2-06.4.2.D - The last sheet provided in this set shows sheet "24 of 27", if this is the last sheet should in not be "27 of 27"?

2. 2-06.4.2.D - All sheets provided in the revision set should have the total number of sheets updated to reflect "27".

3. 2-06.4.5 - The drawing index should have the total number of sheets updated to match the 27 provided.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

4. 2-06.4.9.L - An access easement is required for "DECORATIVE PAVER" area shown on the plan. Provide the recordation information on the plan.

5. 2-06.4.9.W - A separate sign permit will be required for the signage shown on the monument wall.

6. Clarify why sheets that are not being revised have been provided in this set.

7. The provided revision letter references sheet "18A" but no sheet "18A" was provided in the drawing set.

8. The provided revision letter references sheet "27" but no sheet "27" was provided in the drawing set.

9. Provide documentation that the Bridges Design Review has seen and approved the proposed revision.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
04/13/2020 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Passed