Permit Number: DP19-0015
Parcel: 128100570

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0015
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2019 SBEASLE1 START PLANS SUBMITTED Completed
01/25/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0015

1) Per City of Tucson Administrative Manual (AM) section 2-06.4.7.B add the required hold harmless note and drainage will remain it is natural state note
01/28/2019 ELISA HAMBLIN ZONING REVIEW Needs Review
01/28/2019 EHAMBLI1 LANDSCAPE REVIEW Needs Review
01/29/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
Activity Number: DP19-0015
Project Description: GRADING/SWPPP - TEXAS INSTRUMENTS TUCSON
The review has been completed and a resubmittal is required.
To see review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.)
Prepare a Comment Response Letter detailing changes to the plan and which review comments are being addressed.
After the necessary corrections have been made, submit the following items to the PDSD Filedrop at
https://www.tucsonaz.gov/file-upload-pdsd. Please enter the Activity Number in the Project Description field and name the file as directed, for example, second submittal: 2_Plan_Set.pdf. The plans will then re-enter a 20-working-day review cycle.­
1) Comment Response Letter
2) Corrected plan set with all documents
3) Items requested by review staff
The current fee balance is $0 (zero). John Van Winkle, copied, is the Project Manager to contact with any questions, email: John.VanWinkle@TucsonAz.gov or phone: (520) 837-5007. Thank you.

Sharon Beasley
City of Tucson
Planning and Development Services
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
01/29/2019 SBEASLE1 OUT TO CUSTOMER Completed