Permit Number: DP19-0014
Parcel: 141114050

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP19-0014
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2021 SBEASLE1 ENGINEERING REVIEW Approved Approved by Loren Makus, 07/09/21 (during the recent OK to Submit).
08/03/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The revised building FFE’s and manhole rim elevations have resulted in changes to the buildings requiring backwater valves. Buildings 1 and 2 currently are shown with backwater valves but buildings 3, 7, 8, and 9 require the addition of backwater valves. Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole in the public sewer or private sewer collection system, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.
08/05/2021 STEVE SHIELDS ZONING REVIEW Approved
08/10/2021 JPEELDA1 FIRE REVIEW Reqs Change Provide the type of construction for each building.
Provide the fire flow data for the hydrants from Tucson Water

Questions:
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
08/11/2021 AWARNER1 LANDSCAPE REVIEW Approved
08/20/2021 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Email from: COTDSDPermits
To: Jeff Stanley
Fri 8/20/2021 10:28 AM

REVISION Returned for Corrections: DP19-0014

DESCRIPTION: SITE/GRADING/SWPPP - Lot 42 Brown/Rita Ranch. 9013 E OLD VAIL RD

Revision fee balance: $0 (zero) Thank you for the payment.

INCLUDE IN YOUR RESUBMITTAL
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set pages/sheets for revision
3) Any other documents requested by review staff

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then enter permit number)

SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab and you will see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services
Email for Development Pkgs: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)
Email for Building Permits: PDSDinquiries@TucsonAz.gov