Permit Number: DP18-0301
Parcel: 128100570

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP18-0301
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2019 SBEASLE1 START PLANS SUBMITTED Completed
04/02/2019 ANDREW CONNOR LANDSCAPE REVIEW Approved
04/05/2019 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Section Manager

PROJECT: Administrative Office -
Development Package (1st Review) 301 or 251 S Williams Boulevard
DP18-0301 - PAD 1 Zoning

TRANSMITTAL DATE: April 5, 2019
DUE DATE: April 3, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is December 13, 2019.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

2-06.4.7.A.8 - For development package documents provide:

2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

1. COMMENT: Within the parking calculation you state "300 SPACES WILL BE COVERED PARKING). Clearly show the proposed parking covers on the plan. Clearly demonstrate that UDC Article 7.4.6.F.2.a.(1) is addressed.

2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

2. COMMENT: Zoning acknowledges that you intend to use the adjacent sites to fulfill your vehicle parking requirements. Provide the last approved DP/site plan so that parking requirements can be verified. Also per UDC Article 7.4.6.B.1.d provide a copy of the recorded parking agreement.

3. COMMENT: Zoning acknowledges the location of the charging stations. Clearly demonstrate that the charging units will not encroach into the 18' parking space depth.

2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

4. COMMENT: Zoning acknowledges that the long term bicycle parking will be located within the building. Provide a detail that demonstrates how the requirements of UDC Article 7.4.9.D are met.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
04/09/2019 JOHN VAN WINKLE ENGINEERING REVIEW Approved
04/10/2019 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Approved
04/10/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
Activity Number: DP18-0301
Project Description: E SITE/GRADING/SWPPP - Texas Instruments.
To view review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.) After all corrections are made, name your documents accordingly, for example, a 3rd submittal document would be titled: 3_Plan_Set.
Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, enter the Activity Number.
1) Comment Response Letter (lists changes to the Plan and which reviewer comments are being addressed)
2) Corrected Plan Set (all pages, full set)
3) Items requested by review staff
After resubmittal, the plans will re-enter the standard 20-working-day review cycle. The fee balance is $0 (zero). The Project Manager can be reached via email: John.VanWinkle@TucsonAz.gov or phone: (520) 837-5007.
Thank you.
Sharon Beasley

City of Tucson
Planning and Development Services
Attn: Permit Counter
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
04/10/2019 SBEASLE1 OUT TO CUSTOMER Completed