Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP18-0282
Parcel: 11310001A

Address:
1545 E COPPER ST

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP18-0282
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP18-0282

1) Provide on plans waste stream calculations per City of Tucson (COT) Technical Standards Manual (TSM) section 8-01.8.0
2) Provide a SWPPP report upon next submittal
3) Add DP18-0282 to all sheets
4) Provide dimensions of existing sidewalk along Copper St. It appears that the proposed entry gates onto campus interfere with the sidewalk. Enlarge sidewalk width around entry gates or reposition entry gates if needed
5) Engineering can conduct an expedited electronic review once the above comments and any outstanding review comments have been addressed. Please send an email to schedule

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
01/02/2019 SBEASLE1 ADA REVIEW Approved
01/11/2019 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Approved
01/11/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Plans Returned for Corrections (RFC) Notice: DP18-0282
Project Description: E SITE/GRADING/SWPPP - SALPOINTE CATHOLIC H.S. CENTER FOR THE ARTS

The review has been completed and a resubmittal is required.
To see review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number.
(If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.)
Prepare a Comment Response Letter detailing changes to the plan and which review comments are being addressed.
After the necessary corrections have been made to the plans, go to the PDSD Filedrop web page.
Please enter the Activity Number in the “Project Description” field and name the files as directed, for example, second (2nd) submittal: 2_Plan_Set.pdf.
Submit the following items to the PDSD Filedrop at www.tucsonaz.gov/file-upload-pdsd.
The plans will then re-enter a 20-working-day review cycle.­
1) Com­­ment Response Letter
2) Corrected plan set with all documents
3) Items requested by review staff

The current fee balance is $ 1,999.06 (see image below). Review fees must be paid prior to the second submittal review. Please include your Activity Number on the check stub.
Nicholas Ross, copied, is the Project Manager to contact with any questions, email: Nicholas.Ross@TucsonAz.gov or phone: (520) 837-4029.
Thank you.

Sharon Beasley
City of Tucson
Planning and Development Services
201 N. Stone Avenue, First Floor­
Tucson, AZ 85701
12/03/2018 SBEASLE1 START PLANS SUBMITTED Completed
12/03/2018 CHRIS POIRIER PIMA COUNTY ADDRESSING Passed
12/03/2018 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed PAG notified as an FYI only.
12/03/2018 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Passed TEP notified as an FYI only.
12/03/2018 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed USPS notified as an FYI only.
12/03/2018 SBEASLE1 PIMA COUNTY PAG - Pima Association of Governments Passed PAG notified as an FYI only.
12/03/2018 SBEASLE1 UTILITIES SOUTHWEST GAS Passed SW Gas notified as an FYI only.
12/04/2018 MASHFOR1 COT NON-DSD FIRE Approved Per the 2018 International Fire Code - 903.2.1 An automatic sprinkler system shall be provided throughout buildings and portions thereof used as Group A occupancies meeting only one of the four conditions:

*The Fire area exceeds 12,000 square feet

*An operational permit shall also be required for "Places of Assembly" occupancy type
12/12/2018 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
12/19/2018 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved No existing or proposed Tucson Parks and Recreation facilities are affected by this development.

Howard B. Dutt, RLA
Landscape Architect
Tucson Parks & Recreation
(520) 837-8040
Howard.Dutt@tucsonaz.gov
12/26/2018 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL
SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS
4.1 Identification and Descriptive Data
All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.
The landscape plan will contain the following identification in the lower right corner of each sheet:
Any relevant reviews or modifications that affect the site.
Indicate graphically, where possible, compliance with conditions of PAD-17. Exhibit C.3.12: Landscape Border Plan, 3.11 General Landscape and Screening Guidelines and 3.13 Screening Plan.
Ensure that all Zoning and Engineering comments are addressed.
Additional comments may apply.
12/27/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.5 and 708.5, IPC 2012.
12/31/2018 ELISA HAMBLIN ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Elisa Hamblin, AICP
Principal Planner

PROJECT: Salpointe Catholic High School Center for the Arts (1545 E Copper St)
Development Package (1st Review), DP18-0282

TRANSMITTAL DATE: December 31, 2018
DUE DATE: January 2, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is December 2, 2019.

1. 2-06.3.5 - A three-inch by five-inch space shall be reserved in the lower right quadrant of each sheet for an approval stamp. As an electronic submittal, the approval stamp will be added electronically. Ensure a reserved area is located in the same location on each sheet.

2. 2-06.3.8 - The north arrow, contour interval, and scale as applicable to each sheet should be placed together in the upper right corner of each sheet. Sheets 13-19 should have the information placed as indicated.

3. 2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines. Provide landscape architect information on the cover sheet with architect, civil engineer and owner information which has already been provided.

4. 2-06.4.2.B - A brief legal description and a statement as to whether the project is a resubdivision are to be provided in the title block on all sheets.

5. 2-06.4.7.A.6.a - Add a general note that the site is subject to the Major Streets & Routes Overlay, UDC Article 5.4.

6. 2-06.4.7.A.8. - On sheet 1, clarify the onsite facilities table which includes the square footage for each building on site. Provide an existing total. Provide a proposed total (which subtracts the demo and adds the new building). Provide total square footage for the site at the time of PAD adoption in 2009. Provide a total for square footage expansion since 2009 and include an expansion percentage. Additional comments may be forthcoming.

7. 2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. Full dimensions have not been provided.

8. 2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. Zoning boundaries have not been clearly defined.

9. 2-06.4.9.H.2 - Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

10. 2-06.4.9.H.5.a - Clarify the number of existing parking spaces. Sheet 1 lists 520 spaces as existing. Sheet 5 lists 497 spaces as existing.

11. 2-06.4.9.R - Provide dimensions for pedestrian circulation per PAD section 3.5 (pg. 64). Sidewalks must be a minimum of 3-4 ft in width dependent on location.

If you have any questions about this transmittal, please contact me at Elisa.Hamblin@tucsonaz.gov or (520) 837-4966.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
12/31/2018 EHAMBLI1 ZONING HC REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2019 SBEASLE1 OUT TO CUSTOMER Completed