Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP18-0132
Parcel: 140420940

Address:
2900 E ELVIRA RD

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP18-0132
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2018 MARTIN BROWN FIRE REVIEW Approved
06/21/2018 DAVID RIVERA H/C SITE REVIEW Reqs Change See zoning comments:

1. Assure that the new sidewalk is accessbile. Label the horizontal and cross slopes.
06/21/2018 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: SION Power Test Equipment Building - Use is Unclear as of this review
Development Package (1st Review)
DP18-0132 - I-1 Zoning

TRANSMITTAL DATE: June 21, 2018
DUE DATE: July 7, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is June 1, 2019.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section


2-06.3.4 - A title block shall be provided in the lower right quadrant of each sheet.

1. COMMENT: The title block on the survey sheet shall match sheets 1-4. If the survey sheet is not intended to be part of the development package remove it from the sheet index and indicate by response that it is being included for reference only. If Survey sheet is to be included as part of the DP package, remove the word Sequence from upper and lower right sides of the survey sheet.


2-06.3.5 - A three-inch by five-inch space shall be reserved in the lower right quadrant of each sheet for an approval stamp.

2. COMMENT: If the Survey sheet is to be included as part of the Development Package, add the PDSD Approval Stamp in the lower right corner of the sheet.


2-06.3.12 - An index of sheets in the development package shall be provided on the first sheet.

3. COMMENT: Remove from the sheet index sheets that have not been included in the DP package. See related comments 1 and 2 regarding the Survey Sheet.


CONTENT REQUIREMENTS

2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.

4. COMMENT: Add the name, email address and phone number of Owner/developer, and any registrant listed on the cover sheet. Review the list and add the missing information for owner and registrant.


2-06.4.2 - The title block shall include the following information and be provided on each sheet:
2-06.4.2.B - A brief legal description and a statement as to whether the project is a re-subdivision are to be provided. On re-subdivisions, provide the recording information of the existing subdivision plat;

5. COMMENT: The information listed in the title block of sheets 1-4 shall also be listed on the survey sheet if it is to be part of the DP.


2-06.4.2.C - The number of proposed lots and common areas are to be noted. If the subdivision is a Flexible Lot Development (FLD), a condominium, or a similar type of residential subdivision utilizing special provisions of the UDC, it shall be so noted;

6. COMMENT:


2-06.4.2.D - The page number and the total number of pages in the package (i.e., sheet xx of xx).

7. COMMENT: If the survey drawing is included as part of the DP package, add the sheet number and number sheets in the lower right corner next to the title block.


2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

8. COMMENT: Provide the development package case number, DP18-0132, adjacent to the title block on each sheet.


2-06.4.4.B - Identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and,

9. COMMENT: Label the following street names on the location map; Tucson Boulevard, Elvira Road, Tucson Boulevard, and Valencia Road. (See Redlines)


2-06.4.4.C - Section, township, and range; section corners; north arrow; and the scale will be labeled.

10. COMMENT: Label the section corners at the top of the location map. (See redlines)


2-06.4.5 - When the development package documents consists of more than one sheet, a sheet index (a legible drawing of the site showing the area represented on each sheet) is to be placed on the cover sheet or the second sheet.

11. COMMENT: Remove any sheet reference in the sheet index that are not included or part of the DP. (See Redlines)


2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

12. COMMENT: Clarify what is the use of the property. Indicate on the cover sheet under General note 4 if the use is for an administrative professional office, medical office, research and development, General Manufacturing etc. and include the applicable use specific standard. Also please clarify what the new building is to be used for. The note indicates "test equipment building", there is no such use in the code. If this facility is a use such as a "Research and Development" use where prototypes are being developed and tested the proposed use of the new building would be an accessory use to the primary use of the facility. As of this review it is not very clear. The type of testing needs to be clarified as well.


2-06.4.7.A.8.a - Floor area for each building;

13. COMMENT: In the UDC there is no longer a Floor Area Ratio requirement. Under general note 3 remove the floor area ratio notation and just list the square footage of the new building. (See Redlines)


2-06.4.7.A.8.c - Percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included; and,

14. COMMENT: Under the building area notes section, include an expansion calculation based on the proposed SF to existing SF. Remove the reference to Floor area Ratio as there is no limit to the square footage in the UDC. (The building size is limited only by setbacks, height limitations, landscape buffers and parking and loading are requirements.)


2-06.4.7.A.8.d - When the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed. If the project is being phased, calculations must show that, at each phase, requirements are being met.

15. COMMENT: Clarify what is the primary use of the facility. Is the office use subordinate to the manufacturing use or the other way around? In order to verify what the use of the new building is to be considered whether and accessory or primary use, the uses as listed need to be clarified. Additional comments could be forthcoming based on the clarification to this and similar comments above related to the uses.


2-06.4.8 - Existing Site Conditions

The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

16. COMMENT: Provide the information along the west perimeter property boundary as noted by the standard above. (It appears that the area within fifty feet is mainly driveways and landscaping.)


2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

17. COMMENT: Include a curb to property line dimension for Elvira Road.


2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements.

18. COMMENT: Label the zoning classification for the parcels along the north side of Elvira Road. If 17 total accessible spaces are provided, 3 of the spaces must be van accessible. Revise the accessible parking spaces calculation to reflect 3 van accessible spaces have been provided.


2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

19. COMMENT: As noted in other comments above, once the primary use is noted the vehicle parking calculation can be verified for compliance. Again clarify if the is a primary use on this site or are there multiple uses?


2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

20. COMMENT: Indicate the locations of the Long term Bicycle parking facilities. Include a fully dimensioned detail drawing of the long term facility based on the actual location(s).


2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

21. COMMENT: Demonstrate the pedestrian connection from the new sidewalk to the entrance of the new building.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
06/28/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site drawing to include the following utility information:
a. The proposed point of connection to the existing public sewer.
b. The invert and rim elevation of the upstream and downstream manholes along with the Pima County Wastewater Management Department (PCWMD) reference numbers for the manholes.
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2012.
07/03/2018 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ARTICLE 7: DEVELOPMENT STANDARDS
7.6. LANDSCAPING AND SCREENING
7.6.2. APPLICABILITY
The provisions of this section apply to the following:
A. All new development; and,
B. Expansion of existing development, as provided below:
1. Buildings Greater Than 10,000 Square Feet
On sites where the gross floor area of the existing building(s) is more than 10,000 square feet, expansion in square footage of land area, floor area, lot coverage, or vehicular use area as follows:
a. If the expansion is less than 25%, the standards of this section apply only to the proposed expansion. Existing development on the site is subject to the zoning standards in effect at the time the existing development received zoning approval.
b. If the expansion is 25% or greater or if expansions as of February 15, 1991, cumulatively result in a 25% or greater expansion in land area, floor area, lot coverage, or vehicular use area, the standards of this section apply to the entire site.

Provide percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included.

If applicable: Show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-11.0.0, Landscape Plan Requirements.

Ensure that all Zoning and Engineering comments and concerns are addressed.
Additional comments may apply
07/03/2018 ANDREW CONNOR NPPO REVIEW Approved
07/05/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP18-0132

1) Provide curb access ramps linking the western sidewalk (along the fence line) to the southern building entrance.
2) Show on plans that any roof drains (downspouts) scupper underneath sidewalks or pedestrian walkways. Reference TSM section 7-01.4.1.E.
3) Provide waste stream calculations on plans per TSM section 8-01.8.0 in order to verify that current trash enclosure is adequate for proposed expansion.
4) Site plan key notes. C.O.T Standard Details have been replaced by Pima Association of Governments (PAG) standard details Refer to the following link and where applicable reference appropriate PAG standard details. http://apps.pagnet.org/standardspecifications/
5) The Northing and Easting table on sheet 4 references a series of points which aren't shown anywhere on the plans. Show spot elevations on plans.

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007

Final Status

Task End Date Reviewer's Name Type of Review Description
07/05/2018 FERNE RODRIGUEZ REJECT SHELF Completed