Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP18-0131
Parcel: 14043013B

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP18-0131
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2018 DAVID RIVERA ZONING REVIEW Approved
06/29/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP18-0131

1) Provide a letter from Tucson Airport Authority (TAA) accepting the conclusions of the drainage statement found on sheet C002 or provide a complete drainage report for the proposed development. TAA continues to require appropriate drainage reports for airfield projects and monitors the increase in impervious area, as required to insure that staged detention requirements are met.
2) Project development is over one acre. Provide a complete SWPPP, to accompany sheets C600-C602, prior to the pre-construction meeting.
3) Engineering can conduct an over the counter review once the above comments are addressed.

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007

Final Status

Task End Date Reviewer's Name Type of Review Description
07/02/2018 KROBLES1 OUT TO CUSTOMER Completed