Permit Number: DP18-0104
Parcel: 132130680

Review Status: Completed

Review Details: DEV PKG - REVISION

Permit Number - DP18-0104
Review Name: DEV PKG - REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2018 EHAMBLI1 START PLANS SUBMITTED Completed
12/05/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP18-0104

1) Sheet 6. For the proposed the solar canopy, covering the east-west running sidewalk, revise the column alignment so that the columns are centered on the parking stripe. As currently shown they are less than 2.5' away from the edge of curb.

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
12/06/2018 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change UNIFIED DEVELOPMENT CODE
7.6. LANDSCAPING AND SCREENING
Vehicular Use Areas

Canopy Trees in Vehicular Use Areas

General Standards
Within a vehicular use area, one canopy tree is required for each four motor vehicle parking spaces or fraction thereof.

(1) The canopy trees must be evenly distributed throughout the vehicular use area. Every parking space must be located within 40 feet of the trunk of a canopy tree (as measured from the center of the tree trunk).

Portion of the parking lot in the southwest corner of Sheet 19 of 28 does not meet the canopy tree requirement. Revise plan as necessary for approval.
12/06/2018 MASHFOR1 COT NON-DSD FIRE Approved
12/12/2018 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
12/17/2018 AHINES2 ZONING HC REVIEW Reqs Change See zoning comments.
12/17/2018 ALEXANDRA HINES ZONING-DECISION LETTER REVIEW Reqs Change Plans Returned for Corrections (RFC) Notice: DP18-0104
Project Description: E SITE/GRADE/SWPPP - GEICO AT THE BRIDGES

The review has been completed and a resubmittal is required.

To see review comments about the plans, visit PRO at www.tucsonaz.gov/PRO, then search by activity number.
(If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.)

Prepare a Comment Response Letter detailing changes to the plan and which review comments are being addressed. After the necessary corrections have been made to the plans, submit the following items to PDSD Filedrop at www.tucsonaz.gov/file-upload-pdsd.
The plans will then re-enter the 20-working-day review cycle.
1) Comment Response Letter
2) Corrected plan set
3) Items requested by review staff

Please type the activity number in the Project Description and name the files as described on the PDSD Filedrop web page.
The current fee balance is $511.50.

Alexandra Hines, copied, is the Project Manager to contact with any questions: (520) 837-6975.
Thank you.

Alexandra Hines

City of Tucson
Planning and Development Svcs. Dept.
201 N. Stone Ave., First Floor
Tucson, AZ 85701
12/17/2018 ALEXANDRA HINES ZONING REVIEW Reqs Change 12/14/18
Lisa,

I have reviewed the revisions and I would like to see the detail for the solar structure over the parking area that includes the Accessible parking spaces.

I also need to see the height clearance from design grade to the underside of the of the structure of the tallest side. The same height dimensions shall be provided on the other detail I am requesting.

I think the other detail can be added to the sheet 3 next to Solar detail 1.

If the sheet 3 can be revised and resubmitted I can approve the revisions. You'll have to talk to Alex about the change or swap out of sheet 3 if it is updated.

David Rivera
David.Rivera@tucsonaz.gov
Zoning Review Section
Planning & Development Services Department
(520) 837-4957

Final Status

Task End Date Reviewer's Name Type of Review Description
12/17/2018 AHINES2 OUT TO CUSTOMER Completed