Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP18-0014
Review Name: DEV PKG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/18/2018 | ALEXANDRA HINES | START | PLANS SUBMITTED | Completed | |
02/12/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
02/14/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | Show how the site will make maximum use of rainwater runoff for landscape watering. Provide curb openings and depressed landscape areas. UDC 7.6.6.C.2. |
02/15/2018 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | Unified Development Code 4.1 Identification and Descriptive Data A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. B. The landscape plan will contain the following identification in the lower right corner of each sheet: Any relevant case number for reviews or modifications that affect the siteStreet Landscape Borders Minimum Width Street landscape borders must be a minimum of ten feet wide as measured from the street property line. Located on Site Street landscape borders must be located entirely on site, except that, if approved by the City Engineer or designee, up to five feet of the required ten foot width may be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets. Obtain permission for landscaping in public Right of Way. Use of the Public Right-of-Way Nonrequired landscaping may be placed in the public right-of-way, if the following standards are met: 1. The landscaping is approved by the City Engineer or designee and complies with the City Engineer's standards on construction, irrigation, location, and plant type; 2. All vegetation complies with the standards of Section 7.6.4, Landscaping Standards; and, 3. The landscaping does not interfere with the use of the sidewalk. 7.6.5. SCREENING STANDARDS Screening for individual land uses and zones must be provided as determined in Table 7.6.4-1 and in addition to the required landscape borders. Screening is not required between similar uses in accordance with Table 7.6.4-1. Identify all screening elements on landscape plan. Ensure that all Zoning and Engineering comments are addressed. Additional comments may apply. |
02/15/2018 | AHINES2 | ZONING HC | REVIEW | Reqs Change | See Zoning Comments. |
02/16/2018 | JPEELDA1 | FIRE | REVIEW | Approved | |
02/16/2018 | ALEXANDRA HINES | ZONING | REVIEW | Reqs Change | FROM: Alexandra Hines, Lead Planner - Zoning Review PROJECT: DP18-0014 KE&G Office Building (1st Review) at 4101 E Irvington Rd TRANSMITTAL DATE: February 13, 2018 DUE DATE: February 15, 2018 COMMENTS: Please resubmit revised drawings along with a detailed comment response letter that details how all previous comments have been addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use, Administrative Professional Office, as listed in the City of Tucson Unified Development Code (UDC) and the UDC Technical Standards Manual (TSM). UDC 3.3.3.G.5.c, an applicant has one year from the date of application to obtain approval. View the code section for further information on any comment. 1. 2-06.3.5 - Remove the Development Package PDSD Approval stamp from all sheets. Reserve a three-inch by five-inch space in the lower right quadrant of each sheet for an approval stamp. The approval stamp will be applied electronically. 2. 2-06.4.1 - Provide the name, mailing and email addresses, and phone number of the firm, ARC Studios, that prepared the development package documents on the cover sheet. 3. 2-06.4.2.B - Provide the recorded information or a subdivision application for the proposed parcel 1, 2 & 3 on the plan. The existing legal description for 13225069G, 13225069E, and 13225069F is Alvernon Manor Lots 27 & Ptn 26 & Ptn 28 Blk C Exc S45', Alvernon Manor S Ptn Lot 28 Blk C, and Alvernon Manor Lot 29 & Ptn Lot 28 Blk C. Depending on the option, a lot combo or covenant may be needed. 4. 2-06.4.3 - Provide the relevant activity number, DP18-0014, adjacent to the title block on each sheet. 5. 2-06.4.4.A - Show the subject property approximately centered within the one square mile area of the location map. 6. 2-06.4.7.A.4 - List the use specific standards applicable, 4.9.13.Q, to the proposed use. 7. 2-06.4.7.A.6.a - UDC 5.6 - Provide a general note of the type of overlays applicable, Airport Environs Zone (AEZ), and note if the specific criteria is met. 8. 2-06.4.7.A.6.b - If there is more than one lot within the site, the note should specify which lots are affected by the additional applications, 13225069F looks to be divided to create parcel 3 easement area. 9. 2-06.4.7.A.7 - If the property is part of a subdivision plat that is being reviewed or has been recorded, provide the activity number in the lower right corner of each sheet. 10. 2-06.4.7.A.8.c - Provide the expansion and demolition percentage of site coverage for buildings and vehicular use areas. Include the calculations, if the buildings or vehicular use areas have been previously expanded. This will help for the current and future proposals. 11. 2-06.4.8 - Indicate the existing conditions, structures and vehicle use area, on site, 13225069G. 12. 2-06.4.8 - Draw where the adjacent parcel lines meet the property line. 13. 2-06.4.8.A - Indicate information from 2-06.4.2.B comment. Or provide existing site boundary/subdivision perimeter information. 14. 2-06.4.9.A - Indicate information from 2-06.4.2.B comment. Or this section may be applicable. 15. 2-06.4.9.B - Indicate information from 2-06.4.2.B comment. Or this section may be applicable. 16. 2-06.4.9.E - Indicate information from 2-06.4.2.B comment. Or this section may be applicable. 17. 2-06.4.9.F - Clearly define the zoning boundaries on all existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way). 18. 2-06.4.9.H.4 - Indicate if existing streets are public or private. 19. 2-06.4.9.H.5 - UDC 7.4.6 - Dimension width of PAAL south of existing building. 20. 2-06.4.9.H.5 - UDC 7.4.6 - Dimension width of access lane to Irvington. 21. 2-06.4.9.H.5.a - UDC 7.4.6-A - Dimension motor vehicle parking spaces, including, but not limited to, length of angled spaces. 22. 2-06.4.9.H.5.a - Need space/route between first two ADA spaces for access for second two ADA spaces. 23. 2-06.4.9.H.5.a - UDC 7.4.6-A - Specify angle of motor vehicle parking spaces south of existing building. 24. 2-06.4.9.H.5.a - UDC 7.4.4-1 - Provide the parking ratio, 1 to 300. 25. 2-06.4.9.J - Draw the Major Street right-of-way lines for the street, Irvington. Add the MS&R future sidewalk, right-of-way lines, sight visibility triangles, etc. 26. 2-06.4.9.O - Dimension building setback lines for zoning. 27. 2-06.4.9.Q - Provide the height of each proposed and existing structure, covered parking canopy and covered walk, within footprint or site note. 28. 2-06.4.9.Q - UDC 7.4.6.F.2 - Provide enough height of the covered parking canopy in the PAAL or setback from PAAL. 29. 2-06.4.9.Q - Provide the height and specific use proposed within the footprint of the building. 30. 2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code is required. 31. Indicate keynote 22 on sheet 4 or remove from plan. Additional review comments may be forthcoming due to response to zoning review comments or other review agency comments including owner driven changes to the plan. If you have any questions about this transmittal, please contact Alexandra Hines at (520) 837-6975 or Alexandra.Hines@tucsonaz.gov. |
02/21/2018 | KELLY LEE | ZONING-DECISION LETTER | REVIEW | Reqs Change | This review has been completed and resubmittal is required. Please resubmit the following items to PDSD Filedrop https://www.tucsonaz.gov/file-upload-pdsd: 1) Revised Plan Set 2) All approved documents submitted previously 4) All items requested by review staff 5) All items needed to approve these plans Please remember to name your files appropriately, for example: Example 2 (second submittal): 2_plan_set.pdf 2_soils_report.pdf |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/06/2018 | AHINES2 | OUT TO CUSTOMER | Completed |
03/06/2018 | AHINES2 | REJECT SHELF | Completed |