Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The submitted data appears to show the rim elevations of the upstream and downstream manholes approximately 4-feet below the surface of the roadway if your contours are accurate Provide the rim elevations for the manholes as part of this development package, not as a deferred submittal during construction. If the rim elevation of the manhole upstream from the new sewer connection is less than 12" below the first floor elevation of the building, a backwater valve (not a backflow prevention device) will be required. If the first floor elevation is 12" or more above the rim elevation of the manhole, no backwater valve is to be installed. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson.
03/06/2018 SSHIELD1 HC SITE REVIEW Approved
03/06/2018 STEVE SHIELDS ZONING REVIEW Approved