Permit Number: DP17-0238
Parcel: 113081060

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP17-0238
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2018 SSHIELD1 ZONING HC REVIEW Approved
01/02/2018 MARTIN BROWN COT NON-DSD FIRE Reqs Change Once again, please see previous comments. Fire sprinklers are required. Fire lane signs need to have correct verbiage and size. See our website for exact dimentions.
-Signs shall read: Fire access Tow-Away with the no parking symbol.
-Per IFC 2012, 903.2.8 Group R. An automatic sprinkler system shall be provided.
-Code analysis on architectual plans cover sheet also indicate sprinklers will be installed.
01/02/2018 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Principal Planner

PROJECT: Blacklidge Development - Units 1-13
Development Package (2nd Review)
DP17-0238

TRANSMITTAL DATE: January 2, 2018
DUE DATE: January 2, 2018


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is September 26, 2018.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)

2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

7. This comment was not addressed correctly. The setback should be 10' or ¾ the height not 2/3 the height. That said it appears that the structures do meet the required perimeter yard setback of ¾ of 24 or 18'. COMMENT: The required interior building setbacks for this development are based on the greater of 10 feet or ¾ the height of the wall adjacent to the interior property line, see section 6.3.3.C and section 6.3 table 6.3-2.A Non-residential use to Residential Zone.

Once the comment above is addressed Zoning is willing to provide an over the counter review. Call or email to schedule an appointment for this review.
If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development packag
01/02/2018 ALEXANDRA HINES ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:
1) Two rolled sets of the plans
2) All approved documents submitted previously
3) A disk containing all items submitted
4) All items requested by review staff
5) All items needed to approve these plans
12/01/2017 QJONES1 START PLANS SUBMITTED Completed
12/29/2017 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change The following was not addressed from the previous review.



a. One canopy tree is required for every 33 linear feet of landscape border or fraction thereof, excluding vehicular ingress or egress points.
Canopy Tree
b. A woody plant, other than a palm tree, with a mature crown diameter of at least 15 feet and having a trunk that, at maturity, is kept clear of leaves and branches at least six feet above grade.
c.
Verify that Caesalpinia pulcherrima "Standard" meets the minimum canopy requirements

Ensure that Zoning and Engineering comments are addressed.

Additional comments may apply.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2018 KROBLES1 OUT TO CUSTOMER Completed