Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP17-0046
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2017 MMENDIB1 ZONING REVIEW Needs Review
06/02/2017 MMENDIB1 HC SITE REVIEW Needs Review
06/02/2017 MMENDIB1 ENGINEERING REVIEW Needs Review
06/02/2017 MMENDIB1 LANDSCAPE REVIEW Needs Review
06/02/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The placement of the backwater valve does not protect the grease waste piping in the building. Relocate the backwater valve downstream of the point where the grease waste connects to the sanitary waste. [Initial comment: Where the finish floor elevation is below or less than 12 inches above the elevation of the next upstream manhole in the public sewer or private sewer collection system, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor. Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson.]