Permit Review Detail
Review Status: Completed
Review Details: SITE and/or GRADING
Permit Number - DP17-0034
Review Name: SITE and/or GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/16/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/16/2017 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Principal Planner PROJECT: Pima County Housing Development Package (1st Review) DP17-0034 TRANSMITTAL DATE: February 17, 2017 DUE DATE: March 09, 2017 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is February 07, 2018. 2-06.3.0 FORMAT REQUIREMENTS 1. 2-06.3.5 - Provide the PDSD Development Package approval stamp in the lower right quadrant of all sheets. The required stamp can be found at http://pdsd.tucsonaz.gov/pdsd/development-permits under Development Package. 2. 2-06.3.7 - Provide a location map in the upper right hand corner of the cover sheet, see AM Section 2-06.4.4. 3. 2-06.3.8 - Move the north arrow and scale to the upper right corner of each sheet. 4. 2-06.3.12 - Under 'INDEX OF DRAWINGS" you list "SEE MODEL PLAN T16-M0019", this should state Site Plan. CONTENT REQUIREMENTS 5. 2-06.4.1 - Provide the mailing and email addresses, and phone number of the primary property owner of the site on the right half of the cover sheet. 6. 2-06.4.1 - Provide the name, mailing and email addresses, and phone number of the person(s), firm(s), or organization(s) that prepared the development package documents on the right half of the cover sheet. 7. 2-06.4.3 - Provide the development package case number, DP17-0034 , adjacent to the title block on all sheets. 8. 2-06.4.3 - The address shown on the plan is not correct. 9. 2-06.4.3 - Provide the street address adjacent to the title block on all sheets. 10. 2-06.4.4 - Provide a project-location on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information. 11. 2-06.4.4.A - The project location map shall show the subject property approximately centered within the one square mile area; 12. 2-06.4.4.B - The project location map shall identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and, 13. 2-06.4.4.C - Label the Section, township, and range; section corners; north arrow; and the scale on the location map. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 14. 2-06.4.7.A.2 - Provide the acreage of the site on the plan. 15. 2-06.4.7.A.4 - Provide a general note stating the proposed use and any use specific standards that apply. 2-06.4.7.A.8 - For development package documents provide: 16. 2-06.4.7.A.8.a - Provide the floor area for each building on the plan. 17. 2-06.4.7.A.8.a - Provide a density calculation on the plan, see UDC Article 6.4.7. 2-06.4.8 - Existing Site Conditions The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided. 18. 2-06.4.8.A - Provide the site boundary perimeter bearings in degrees, minutes, and seconds. 19. 2-06.4.8.A - The site boundary perimeter distances is not correct. 20. 2-06.4.8.C - The 30' right of way dimension is not shown correctly. This dimension is from the centerline of Ontario to the property line of your parcel. Also provide dimensioned width of paving, curbs, curb cuts and sidewalks. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 21. 2-06.4.9.H.5 - Provide a width dimension for the proposed PAAL. 22. 2-06.4.9.H.5.a - Provide a fully dimensioned vehicle parking area. 23. 2-06.4.9.H.5.a - Provide a standard vehicle parking space detail. This detail should include a location dimension for the proposed wheel stops shown on the plan, see UDC Article 7.4.6.H.3. 24. 2-06.4.9.H.5.a - Provide a large scale detail of the accessible parking space showing all accessible requirements such as dimensions, markings, grade slopes, accessible parking aisle, signage, van accessible space and access to the accessible route. Per the 2012 IBC, Table 1106.1, the accessible vehicle parking space is required to be a van accessible parking space. Demonstrate on the detail that the accessible space meets the requirements of ICC A117.1, Section 502.2. 25. 2-06.4.9.H.5.a - Provide a vehicle parking spaces calculation that shows the number required and provided also the ratio used. 26. 2-06.4.9.H.5.a - Provide a large scale accessible sign detail including a van accessible sign and show the location of the sign on the plan. 27. 2-06.4.9.H.5.d - Provide a short and long term bicycle parking space calculation that provides the number required and provided along with the ratio used. It does not appear that the provided short term bicycle parking calculation is correct, review UDC Table 7.4.8-1. 28. 2-06.4.9.H.5.d - Provide a short term bicycle parking space detail that demonstrates how the requirements of UDC Article 7.4.9.B.1 & .2 and 7.4.9.C are met. 29. 2-06.4.9.H.5.d - Provide a long term bicycle parking space detail that demonstrates how the requirements of UDC Article 7.4.9.B.1 & .2 and 7.4.9.D are met. 30. 2-06.4.9.O - Provide a front street perimeter yard setback dimension on the plan, see UDC Article 6.4.5.C.1. 31. 2-06.4.9.O - It does not appear that the side and rear perimeter yard setback is correct. Per UDC Article 6.3.3.C and UDC Table 6.3-2.A. This setback should be 10' or ¾ the height of the proposed building exterior wall. 32. 2-06.4.9.R - Clearly show the required accessible route from the street sidewalk to the accessible vehicle parking space and to the required accessible unit. Demonstrate on the plan that this route meets the requirements of the ICC A117.1. 33. 2-06.4.9.R - Show the max cross slope of 2% on the accessible ramp detail. 34. 2-06.4.9.T - Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. 35. 2-06.4.9.V - Demonstrate on the plan how mail service will be provided. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 02/17/2017 | SSHIELD1 | ADA | REVIEW | Passed | |
| 02/17/2017 | SSHIELD1 | H/C SITE | REVIEW | Reqs Change | See Zoning comments |
| 02/28/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the site drawing to include the following existing utility information: a. The location and size of water lines, and fire hydrants. b. The location and size of sanitary sewers, including the pipe diameter and the invert and rim elevations of all manholes along with the Pima County Wastewater Management Department (PCWMD) reference number. c. The point of connection to the existing public sewers. d. The locations of gas lines, electric and telephone lines, poles, and communications cables, on-ground junction boxes, and street lights. e. The first floor elevation for the buildings Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2012. |
| 03/09/2017 | JOE LINVILLE | LANDSCAPE | REVIEW | Reqs Change | 1) Submit a landscape plan, including the content specified in AM 2-10.0 2) Provide a street landscape border in accordance with UDC 7.6.4.C.2 3) Provide parking lot screening in accordance with UDC Table 7.6.4-1 |
| 03/09/2017 | JOE LINVILLE | NPPO | REVIEW | Passed | |
| 03/10/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | Provide existing contours and proposed spot grades throughout the site. Clearly indicate that all landscape areas will be depressed a minimum of six inches for water harvesting. Provide scuppers to keep sidewalks flood free for up to a 10-year event. Projects with six or more units require centralized collection. (TSM 8-01.5.1.a) Show container location, access and enclosures for garbage and recycling service. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/07/2017 | MMENDIB1 | OUT TO CUSTOMER | Completed |