Review Details: RESUB - SITE and/or GRADING
Permit Number - DP16-0197
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/15/2016 | ARUIZ1 | ZONING | REVIEW | Needs Review | |
| 12/15/2016 | ARUIZ1 | HC SITE | REVIEW | Needs Review | |
| 12/15/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Reqs Change | 5 year threshold retention is not being provided for the redevelopment area. The drainage inlet elevation is below the surrounding grades shown in the basin. Please see 1st comment letter. |
| 12/15/2016 | ARUIZ1 | LANDSCAPE | REVIEW | Needs Review | |
| 12/15/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The rim elevation of the next upstream sanitary manhole (#6408-07, 2443.20') is less than 12" below the finished floor elevation of the new building (2443.86'). Provide a note on the plans requiring the installation of a backwater valve when future plumbing activities take place. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson. [Initial comment: Revise the site drawing to include the points of connection to existing public sewers. Reference: City of Tucson Administrative Manual No. 2-06.0.0, Section 4.8 and Section 107.2.13, IBC 2012.] |