Permit Number: DP16-0158
Parcel: 14118008F

Review Status: Completed

Review Details: GRADING

Permit Number - DP16-0158
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2016 ANDREW CONNOR NPPO REVIEW Approv-Cond Ensure that all Zoning and Engineering comments and concerns are addressed.
09/30/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 8880 E. Old Vail Road
Grading Plan (1st Review)
DP16-0158

TRANSMITTAL DATE: September 30, 2016

DUE DATE: September 30, 2016

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The grading plan has been reviewed by the Zoning Section but cannot approve the plan until all Engineering, comments, concerns, and appropriate revisions have been addressed.

Once approved by Engineering Zoning is willing to provide an over the counter review. Please call or email to schedule this review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
10/03/2016 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. List DP16-0139 in the list of relevant case numbers on each sheet.
2. This grading plan shows proposed pads not shown on the associated DP16-0139. Provide an explanation in your response letter. The site DP might need to be revised to address this.
3. The plan shows roof drain scuppers discharging into accessible parking spaces and adjacent to access ramps. Move the scupper locations to prevent nuisance ponding in accessible parking and associated ramps.
4. Revise note 11 to include Pima County since PDEQ enforces dust regulations.
5. Revise grading note 26 to provide for a maximum depth of 9 inches in water harvesting areas.
6. Provide a barrier or barrier along the south edge of the vehicle use area to prevent vehicles from driving of the paved surface.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2016 RBENT2 OUT TO CUSTOMER Completed