| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/04/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Principle Planner PROJECT: MHC Healthcare Building Expansion. Development Package (1st Review) DP16-0 TRANSMITTAL DATE: October 4, 2016 DUE DATE: October 18, 2016 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is July 24, 2016. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 1. This comment was not addressed. 2-06.4.9.H.5.a - Detail 2 sheet 2 Wall Mounted Accessible Parking Sign provide a sign mounting height dimension for the van accessible sign. This dimension should be 7'-0". 2. This comment was not fully addressed. Provide a detail for what appears to be a ramp shown on the route to the street that demonstrate how the requirements of ICC A117.1-2009 are met. 2-06.4.9.R - As new accessible vehicle parking spaces are proposed provide an accessible route to the street property line. 3. 2-06.4.9.R - Provide a width dimension for the sidewalk shown near the northwest corner of the proposed addition. This sidewalk must be 4'-0". Additional comments; 4. This comment was not addressed. Provide a copy of the last approved site plan with you next submittal. Depending on what is shown on the plan additional comments may be forth coming. Once the above comments have been addressed Zoning will provide an over the counter review. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 10/04/2016 | SSHIELD1 | H/C SITE | REVIEW | Reqs Change | See Zoning comments |
| 10/05/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 10/12/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | There are two fire hydrants located within 500 feet of the subject property: one is at the northeast corner of West Prince Road and North Flowing Wells Road and the other is about 200-feet east of the property on the north side of West Prince Road. [Initial Comment: Revise the site drawing to include the location of fire hydrants.] |
| 10/14/2016 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approv-Cond | Ensure that all Zoning comments and concerns are addressed. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/21/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |