Permit Number: DP15-0191
Parcel: 205640620

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Permit Number - DP15-0191
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2016 MARTIN BROWN COT NON-DSD FIRE Approv-Cond ADDED CONDITION-COULD NOT FIND COMMENT ON DRAWINGS
01/11/2016 FDILLON1 DESIGN PROFESSIONAL REVIEW Denied This project requires an Architectural Variation Plan (AVP) per UDC Section 8.7.3.M.
01/19/2016 JANE DUARTE COT NON-DSD PARKS & RECREATION Approv-Cond All Parks and Recreation comments have been adequately addressed except for our comment #1 which states:

1) Note #17 on sheet 2 is incorrect and should be revised. According to the current
Pima Regional Trails System Master Plan, there are two trails located on or adjacent
to this property. The Esmond Station and the Atturbury Wash South Fork Greenways
are located on this property...

Revise Note #17 to cite the current COT/Pima County trail planning document as the "Pima Regional Trails System Master Plan" and to recognize the existence on that master plan of the Esmond Station and Atturbury Wash South Fork Greenways which are located on or adjacent to this site. The note should also state that these greenways are accommodated by the inclusion of Non-motorized Trail Easements on the plan for future trail extension by others.


Howard B. Dutt, RLA

Landscape Architect
Tucson Parks & Recreation
(520) 837-8040

Howard.Dutt@tucsonaz.gov
01/20/2016 BVIESTE1 ENV SVCS REVIEW Approv-Cond The Development Package has been reviewed on behalf of the Environmental Services Dept. and is conditionally approved pending the following comment:

· Please correct the phasing labeling on Sheet 8 for Phase One and Two.

If there are any questions, I can be reached at kperry@perryengineering.net
01/20/2016 MPADILL1 COT NON-DSD COMMUNITY PLANNING Approv-Cond Conditional approval subject to the following condition.

Correct Development plan, remove reference to R-2 zone where ever noted. Sheet 2 of 25 makes reference to R-2 zone. Correct all necessary sheets by removing all references to R-2 zone. Site is zoned R-1.
01/22/2016 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:

1) Two rolled sets of the plans
2) All items requested by review staff
3) All items needed to approve these plans
12/23/2015 KROBLES1 START PLANS SUBMITTED Completed
12/29/2015 DAVID RIVERA ZONING REVIEW Approved
12/29/2015 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)



FROM: Janice Wagner
GIS Cartographer
Pima County Assessor's Office


DATE: December 28, 2015


RE: Assessor's Review and Comments Regarding:

FINAL PLAT MOUNTAIN VAIL ESTATES, PART G
S15-051


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor's Office requirements.
_______ Plat does not meet Assessor's Office requirements.

COMMENTS:
12/29/2015 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved Traffic impact analysis to determine traffic signal requirement will be made seperate from Development Plan Process.

Zelin Canchola
TDOT
12/29/2015 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Reqs Change See additional documents in PRO.

Request for Corrections—please see attached plans with Addressing comments attached as sticky notes.
12/30/2015 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change DATE: January 4, 2016
DUE DATE: January 25, 2016
SUBJECT: Mountain Vail Estates, Part G
TO: Warren D. Thompson, PE
LOCATION: 11311 E Mary Ann Cleveland
REVIEWERS: Paul Baughman, PE, CFM
ACTIVITY: DP15-0191
SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed 2nd submittal of Development Plan Package. The following items need to be addressed:
1) Per AM 2-06.4.8H and AM 2-06.4.9N2 and previous 1st submittal comment please show drainage gradients of streets on the site plan. Per a check against the originally approved drainage report, submitted electronically with this 2nd submittal, a 0.58% and 0.57% slope in front of lots 86 - 89 do not match Figure 4 of the developed conditions watershed in the drainage report. Please update the plan or the drainage report.
2) Per AM 2-06.4.8I and AM 2-06.4.9O and 1st submittal comment please show where locally regulated floodplain limits will be located based on developed conditions. Please also show where FEMA floodplain limits will be based on LOMR submittal. All of the existing and developed conditions FEMA and locally regulated floodplain line work should be reflected in the legend. The legend does not reflect the line work used to show the developed conditions floodplain based on the LOMR.
3) Please initiate process with City during review of LOMR, if required by FEMA, to set up any agreements that may be required based on CFR 44 Sec 65.2 and 65.10 maintenance requirements. This will be reviewed with the LOMR submittal.
If you have any comments questions or wish to discuss new information, please call or email me at 520-837-5007 or paul.baughman@tucsonaz.gov.
12/30/2015 BVIESTE1 PIMA COUNTY WASTEWATER Approved Pima County Regional Wastewater Reclamation Department

Jackson Jenkins
Director
201 N. Stone Ave., 8th Floor
Tucson, Arizona 85701-1207

PH: (520) 740-6500
FAX: (520) 620-0135

December 29, 2015

To: Warren Thompson, P.E.
Stantec Consulting Services, Inc

Thru: Patricia Gehlen
City of Tucson Development Services
____________________________________
From: Tom Porter, P.E., PCRWRD (520) 724-6719

Subject: Mountain Vail Estates Part G Lots 1-95
Tentative Plat - 2st submittal
P15WS00043 (DP15-0191)

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer design for the above-referenced project. The Pima County Regional Wastewater Reclamation Department approves the above referenced submittal of the Preliminary Sewer Layout (PSL), based upon PCRWRD Engineering Design Standards (EDS) 2012.

If you have any questions regarding this matter please contact me at your convenience.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/22/2016 AROMERO4 OUT TO CUSTOMER Completed
01/22/2016 PGEHLEN1 REJECT SHELF Completed